APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
80%
90%
100%
110%
120%
Capacity Factor
0.96
0.98
1.00
1.02
1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY
Models
AHE18B
(6ELE6)
AHE22B
AHE24B
(6ELE7)
AHE30B
(6ELE8)
AHE34C
AHE36C
(6ELE9)
AHE42D
(6ELF0)
AHE48D
(6ELF1)
AHE60D
(6ELF2)
Blower - Diameter x Width
10 x 8
10 x 8
10 x 8
10 x 8
11 x 10
11 x 10
11 x 10
11 x 10
11 x 10
Motor
HP
1/3 HP
1/3 HP
1/3 HP
1/3 HP
1/2 HP
1/2 HP
1/2 HP
3/4 HP
3/4 HP
Nominal RPM
1050
1050
1050
1050
1050
1050
1050
1050
1050
Voltage
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
Full Load Amps @230V
2.8
2.8
2.8
2.8
4.1
4.1
4.1
6.0
6.0
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1
Permanent Type Kit
1PF0601BK 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK
Shipping /
Operating Weight (lbs.)
115/103
120/105
120/105
120/105
152/137
152/137
168/150
171/153
174/156
1. Field supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by
the conversion factor in the following table.
DISTRIBUTION POWER
NOMINAL VOLTAGE
CONVERSION FACTOR
220V
240V
0.84
ELECTRICAL DATA - COOLING ONLY
Models
Motor FLA
1
Minimum Circuit
Ampacity
MOP
2
Minimum Wire Size (AWG)
3
AHE18B / AHE22B /
AHE24B / AHE30B
2.8
3.5
15
14
AHE34C / AHE36C / AHE42D
4.1
5.1
15
14
AHE48D / AHE60D
6.0
7.5
15
14
1. FLA = Full Load Amps
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75
C, copper wire only. If wire other than non-plated, 75
C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
ELECTRICAL HEAT: MINIMUM FAN SPEED
1
Heater Kit Models
2,3
Nom. kW
@240V
Air Handler Models
AHE18B
AHE22B
AHE24B
AHE30B
AHE34C
AHE36C
AHE42D
AHE48D
AHE60D
6HK(0,1)6500206
2.4kW
Med Low #2
Med Low #2
Low #1
Med #3
Low #1
Med Low #2
Med Low #2
6HK(0,1)6500506
4.8kW
Med Low #2
Med Low #2
Med Low #2
Med Low #2
Med #3
Med #3
Med Low #2
6HK(0,1)6500806
7.7kW
Med High #4 Med High #4
Med #3
Med #3
Med #3
Med #3
Med Low #2
6HK(0,1)6501006
6HK06501025
9.6kW
Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med High #4
Med #3
6HK(1,2)6501306
12.5kW
-
Med High #4 Med High #4 Med High #4 Med High #4 Med High #4
Med #3
6HK(1,2)6501506
6HK06501525
14.4kW
-
High #5
High #5
Med High #4 Med High #4 Med High #4
Med #3
6HK(1,2)6501806
6HK06501825
17.3kW
-
-
-
High #5
High #5
High #5
Med High #4
6HK(1,2)6502006
6HK16502025
19.2kW
-
-
-
High #5
High #5
High #5
High #5
6HK(1,2)6502506
6HK16502525
24kW
-
-
-
-
-
-
High #5
1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.