Johnson Controls Unitary Products

5

697887-YTG-H-0514

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow (CFM)

80%

90%

100%

110%

120%

Capacity Factor

0.96

0.98

1.00

1.02

1.03

PHYSICAL & ELECTRICAL DATA - COOLING ONLY

Models

AHE18B

(6ELE6)

AHE22B

AHE24B

(6ELE7)

AHE30B

(6ELE8)

AHE34C

AHE36C

(6ELE9)

AHE42D

(6ELF0)

AHE48D

(6ELF1)

AHE60D

(6ELF2)

Blower - Diameter x Width

10 x 8

10 x 8

10 x 8

10 x 8

11 x 10

11 x 10

11 x 10

11 x 10

11 x 10

Motor

HP

1/3 HP

1/3 HP

1/3 HP

 1/3 HP

1/2 HP

1/2 HP

1/2 HP

3/4 HP

3/4 HP

Nominal RPM

1050

1050

1050

1050

1050

1050

1050

1050

1050

Voltage

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Full Load Amps @230V

2.8

2.8

2.8

2.8

4.1

4.1

4.1

6.0

6.0

Filter

1

Type

DISPOSABLE OR PERMANENT

Size

16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1

Permanent Type Kit

1PF0601BK 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK

Shipping / 
Operating Weight (lbs.)

115/103

120/105

120/105

120/105

152/137

152/137

168/150

171/153

174/156

1.  Field supplied.

KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT

For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by
the conversion factor in the following table.

DISTRIBUTION POWER

NOMINAL VOLTAGE

CONVERSION FACTOR

220V

240V

0.84

ELECTRICAL DATA - COOLING ONLY 

Models

Motor FLA

1

Minimum Circuit 

Ampacity

MOP

2

Minimum Wire Size (AWG)

3

AHE18B / AHE22B /

AHE24B / AHE30B

2.8

3.5

15

14

AHE34C / AHE36C / AHE42D

4.1

5.1

15

14

AHE48D / AHE60D

6.0

7.5

15

14

1. FLA = Full Load Amps
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75

C, copper wire only. If wire other than non-plated, 75

C ambient, copper wire is used, consult applicable tables of the NEC and local codes.

ELECTRICAL HEAT: MINIMUM FAN SPEED

1

Heater Kit Models

2,3

Nom. kW

@240V

Air Handler Models

AHE18B

AHE22B
AHE24B

AHE30B

AHE34C
AHE36C

AHE42D

AHE48D

AHE60D

6HK(0,1)6500206

2.4kW

Med Low #2

Med Low #2

Low #1

Med #3

Low #1

Med Low #2

Med Low #2

6HK(0,1)6500506

4.8kW

Med Low #2

Med Low #2

Med Low #2

Med Low #2

Med #3

Med #3

Med Low #2

6HK(0,1)6500806

7.7kW

Med High #4 Med High #4

Med #3

Med #3

Med #3

Med #3

Med Low #2

6HK(0,1)6501006

6HK06501025

9.6kW

Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med High #4

Med #3

6HK(1,2)6501306

12.5kW

-

Med High #4 Med High #4 Med High #4 Med High #4 Med High #4

Med #3

6HK(1,2)6501506

6HK06501525

14.4kW

-

High #5

High #5

Med High #4 Med High #4 Med High #4

Med #3

6HK(1,2)6501806

6HK06501825

17.3kW

-

-

-

High #5

High #5

High #5

Med High #4

6HK(1,2)6502006

6HK16502025

19.2kW

-

-

-

High #5

High #5

High #5

High #5

6HK(1,2)6502506

6HK16502525

24kW

-

-

-

-

-

-

High  #5

1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
3. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.

Summary of Contents for 1CJZ7

Page 1: ...ry installed metering device For added flexibility an R 22 or R 410A TXV or orifice can be field installed to meet your refrigerant choice FEATURE Thermal Expansion Valve Provides the ultimate refrige...

Page 2: ...20 29 32 23 1 2 7 8 1 All dimensions are in inches 2 Actual size conduit size COIL TECHNICAL DATA Models Application Refrig Conn Types Face Area Sq Ft Rows Deep Fins Per In Coil Size Tube Geometry Tub...

Page 3: ...8 12 8 70 57 21 2 18 6 16 2 13 7 795 85 72 50 8 45 2 38 4 32 0 80 67 43 7 36 8 31 24 0 75 62 35 7 29 5 23 1 16 1 70 57 27 9 24 5 21 17 6 985 85 72 64 9 54 45 6 37 8 80 67 52 3 44 6 36 9 28 4 75 62 42...

Page 4: ...51 3 41 5 80 67 56 5 48 2 39 7 29 9 75 62 45 1 36 8 28 3 18 9 70 57 34 4 31 26 8 22 5 1195 85 72 79 5 69 7 59 9 48 6 80 67 65 2 55 5 45 5 34 9 75 62 52 2 42 5 32 6 21 8 70 57 40 1 36 1 31 1 26 2 1385...

Page 5: ...FACTOR 220V 240V 0 84 ELECTRICAL DATA COOLING ONLY Models Motor FLA1 Minimum Circuit Ampacity MOP2 Minimum Wire Size AWG 3 AHE18B AHE22B AHE24B AHE30B 2 8 3 5 15 14 AHE34C AHE36C AHE42D 4 1 5 1 15 14...

Page 6: ...nversion table on Page 5 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 1 60 Air Handler Models Heater Models1 2 Heater Amps 240V Field Wiring Min Circuit Ampacity MOP 3 Min Wire Size AWG 4 20...

Page 7: ...ty MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Circuit 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd AHE22B AHE24B AHE30B 6HK16501306 52 0 22...

Page 8: ...0253 46 2 57 6 65 3 60 70 6 4 6HK165025253 57 7 70 0 79 6 70 80 4 4 1 MOP Maximum Overcurrent Protection device must be HACR type circuit breaker or time delay fuse 2 Stated sizes are for 75 C copper...

Page 9: ...365 287 NA AHE36C High 5 1465 1415 1360 1307 1246 1183 1118 Med High 4 1260 1204 1142 1075 1008 946 876 Med 3 1088 1022 939 862 782 721 626 Med Low 2 998 810 717 630 562 493 444 Low 1 903 707 411 323...

Page 10: ...10 Johnson Controls Unitary Products 697887 YTG H 0514 TYPICAL THERMOSTAT CONNECTION...

Page 11: ...ICAL THERMOSTAT WIRING FOR 2 STAGE HEAT PUMP WITH ECM BLOWER MOTOR A001 001 NOTICE WIRING FOR BLOWER MOTOR MAY REQUIRE FIELD ADJUSTMENT DEPENDING ON MATCHUP OF SYSTEM UNITS REFER TO THE AIR FLOW DATA...

Page 12: ...change without notice Published in U S A 697887 YTG H 0514 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 697887 YTG G 0314 York International Corp 5005 York Drive Norman OK 73...