Johnson Controls Unitary Products

9

697887-YTG-H-0514

LIMITATIONS

These units must be wired and installed in accordance with all
national and local safety codes.

Voltage limits are as follows: 

Airflow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units.

Air Handler Voltage

Voltage code

Normal Operating 

Voltage Range

1

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208/230-1-60

06

187-253

AIR FLOW DATA (CFM)

1

Models

Blower 

Motor Speed

External Static Pressure (in. wc.)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

AHE18B

High #5

1075

1041

1003

970

930

885

842

Med High #4

895

845

808

767

709

647

561

Med #3

663

618

557

490

348

267

192

Med Low #2

629

468

356

197

175

68

23

Low #1

629

468

356

197

175

68

23

AHE22B
AHE24B
AHE30B

High #5

1156

1120

1093

1056

1014

951

862

Med High #4

1021

987

952

918

873

836

787

Med #3

829

789

754

698

654

585

532

Med Low #2

681

621

575

496

435

336

262

Low #1

598

503

437

340

259

203

74

AHE34C

High #5

1471

1429

1387

1337

1289

1233

1172

Med High #4

1301

1248

1198

1147

1008

999

927

Med #3

1097

1044

972

906

815

748

680

Med Low #2

943

868

768

689

617

566

520

Low #1

869

668

515

424

365

287

NA

AHE36C

High #5

1465

1415

1360

1307

1246

1183

1118

Med High #4

1260

1204

1142

1075

1008

946

876

Med #3

1088

1022

939

862

782

721

626

Med Low #2

998

810

717

630

562

493

444

Low #1

903

707

411

323

265

152

NA

AHE42D

High #5

1632

1589

1542

1494

1446

1391

1335

Med High #4

1430

1390

1346

1294

1238

1168

960

Med #3

1238

1198

1145

1082

993

908

805

Med Low #2

1118

1020

947

851

734

666

563

Low #1

998

772

477

418

349

NA

NA

AHE48D

High #5

1861

1823

1787

1750

1708

1666

1620

Med High #4

1674

1640

1599

1562

1516

1472

1432

Med #3

1442

1405

1358

1311

1262

1197

1108

Med Low #2

1257

1220

1163

1103

1031

942

864

Low #1

1153

1031

967

867

764

718

633

AHE60D

High #5

2091

2053

2016

1975

1937

1906

1869

Med High #4

1903

1868

1832

1791

1748

1703

1660

Med #3

1634

1598

1562

1516

1468

1422

1350

Med Low #2

1447

1404

1361

1318

1257

1164

1092

Low #1

1268

1203

1148

1073

978

907

839

1.  Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.30" wc. external static pressure. 

Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.6" are not recommended.
Airflow data shown is from testing performed at 230V. AHE units use a X13 motor, and there is minimal variation of airflow at other distribution voltage values. The 
above data can be used for airflow at other distribution voltages.

Summary of Contents for 1CJZ7

Page 1: ...ry installed metering device For added flexibility an R 22 or R 410A TXV or orifice can be field installed to meet your refrigerant choice FEATURE Thermal Expansion Valve Provides the ultimate refrige...

Page 2: ...20 29 32 23 1 2 7 8 1 All dimensions are in inches 2 Actual size conduit size COIL TECHNICAL DATA Models Application Refrig Conn Types Face Area Sq Ft Rows Deep Fins Per In Coil Size Tube Geometry Tub...

Page 3: ...8 12 8 70 57 21 2 18 6 16 2 13 7 795 85 72 50 8 45 2 38 4 32 0 80 67 43 7 36 8 31 24 0 75 62 35 7 29 5 23 1 16 1 70 57 27 9 24 5 21 17 6 985 85 72 64 9 54 45 6 37 8 80 67 52 3 44 6 36 9 28 4 75 62 42...

Page 4: ...51 3 41 5 80 67 56 5 48 2 39 7 29 9 75 62 45 1 36 8 28 3 18 9 70 57 34 4 31 26 8 22 5 1195 85 72 79 5 69 7 59 9 48 6 80 67 65 2 55 5 45 5 34 9 75 62 52 2 42 5 32 6 21 8 70 57 40 1 36 1 31 1 26 2 1385...

Page 5: ...FACTOR 220V 240V 0 84 ELECTRICAL DATA COOLING ONLY Models Motor FLA1 Minimum Circuit Ampacity MOP2 Minimum Wire Size AWG 3 AHE18B AHE22B AHE24B AHE30B 2 8 3 5 15 14 AHE34C AHE36C AHE42D 4 1 5 1 15 14...

Page 6: ...nversion table on Page 5 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 1 60 Air Handler Models Heater Models1 2 Heater Amps 240V Field Wiring Min Circuit Ampacity MOP 3 Min Wire Size AWG 4 20...

Page 7: ...ty MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Circuit 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd AHE22B AHE24B AHE30B 6HK16501306 52 0 22...

Page 8: ...0253 46 2 57 6 65 3 60 70 6 4 6HK165025253 57 7 70 0 79 6 70 80 4 4 1 MOP Maximum Overcurrent Protection device must be HACR type circuit breaker or time delay fuse 2 Stated sizes are for 75 C copper...

Page 9: ...365 287 NA AHE36C High 5 1465 1415 1360 1307 1246 1183 1118 Med High 4 1260 1204 1142 1075 1008 946 876 Med 3 1088 1022 939 862 782 721 626 Med Low 2 998 810 717 630 562 493 444 Low 1 903 707 411 323...

Page 10: ...10 Johnson Controls Unitary Products 697887 YTG H 0514 TYPICAL THERMOSTAT CONNECTION...

Page 11: ...ICAL THERMOSTAT WIRING FOR 2 STAGE HEAT PUMP WITH ECM BLOWER MOTOR A001 001 NOTICE WIRING FOR BLOWER MOTOR MAY REQUIRE FIELD ADJUSTMENT DEPENDING ON MATCHUP OF SYSTEM UNITS REFER TO THE AIR FLOW DATA...

Page 12: ...change without notice Published in U S A 697887 YTG H 0514 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 697887 YTG G 0314 York International Corp 5005 York Drive Norman OK 73...

Reviews: