background image

5390862-UIM-A-0318

8

Johnson Controls Unitary Products

SYSTEM CHARGING

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. (4.6 m) line set, and the smallest indoor coil match-up.
Some indoor coil matches may require additional charge. See tabular
data sheet provided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.
TOTAL SYSTEM CHARGE is determined as follows:
1.

Determine the Base Charge shipped in the outdoor unit from the
Tabular Data Sheet included with the outdoor unit.

2.

Determine the charge adder for the matched indoor unit from the
Tabular Data Sheet included with the outdoor unit.

3.

If the lineset length is greater than 15 feet (4.6 m), calculate the
charge adder for actual lineset length using the Tabular Data
Sheet included with the outdoor unit.

4.

Once the charge adders for matched indoor unit and for lineset
have been weighed in, verify the system operation against the
temperatures and pressures in the Charging Chart for the outdoor
unit. Locate Charging Charts on the outdoor unit and also in the
Service Application Data on 

www.upgnet.com

. Follow the Subcool

or the Superheat charging procedure in the section below accord-
ing to the type of indoor metering device in the system, and allow
ten minutes after each charge adjustment for the system operation
to stabilize. Record the charge adjustment made to match the
Charging Chart.

5.

Verify that TOTAL SYSTEM CHARGE = Base Charge (as
shipped) + charge adder for matched indoor unit + charge adder
for actual lineset charge adjustments to match Charging
Chart.

6.

Permanently stamp the unit data plate with the TOTAL SYSTEM
CHARGE as defined above.

This method is to be used whenever additional refrigerant is required
for the system charge.

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly. Otherwise, model-specific charging
charts are provided on the access panel of the unit.

SUBCOOLING CHARGING METHOD - TXV INDOOR

The outdoor unit comes equipped with subcooling charts optimized for
that particular unit. Please follow the instructions on the unit. If those
instructions are not readily available, follow the instructions below.
1.

Set the system running in cooling mode by setting the thermostat
at least 6

°

F below the room temperature and operate system for at

least 10 – 15 minutes.

2.

Refer to the technical guide for the recommended indoor airflow
and verify it is correct (it should be 350- 400 SCFM per ton).

3.

Measure and record the indoor wet bulb (WB) and the outdoor
ambient dry bulb (DB) temperature.

4.

Using the charging chart located on the unit, find the intersection
of the indoor wet bulb and the outdoor dry bulb. This is the recom-
mended liquid pressure (and subcooling value).

5.

Measure and record the pressure at the liquid valve pressure port
and compare to the value obtained in step 4.

6.

Add charge if the measured liquid pressure is lower than the rec-
ommended value. Remove / recover charge if the measured liquid
pressure is above the recommended value.

Condenser subcooling is obtained by calculating the difference of the
saturated refrigerant temperature of the pressure measured at the liquid
base valve and the liquid tube temperature as measured at the liquid
base valve.
Subcooling Temp. (TC) = Saturated Temp. (TS) – Liquid Temp. (T).

NOTICE

For cold weather charging of the system at temperatures of 55°F or
below, refer to the “Optional Cold Weather Charging” procedures
near the end of SECTION VI: SYSTEM CHARGE.

 CAUTION

R-410A refrigerant cylinders are rose colored. Always charge the
system slowly with liquid R-410 refrigerant.

 CAUTION

Do not leave the system open to the atmosphere.

 WARNING

DO NOT attempt to pump “Total System Charge” into outdoor unit for
maintenance or service. This may cause damage to the compressor
and/or other components. Recover and weigh “System Charge” into
an appropriate recovery cylinder for any instances requiring evacua-
tion. 

!

!

!

 WARNING

It is recommended to not attempt to pump more than the “Factory
Charge” and an additional 15 foot line charge into a tube and fin out-
door unit for maintenance or service. This can cause damage to the
compressor and/or other components.

 CAUTION

Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.

 CAUTION

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The liquid pressure listed at the intersection of the indoor 
WB and the outdoor DB 320 psig. Pressure at the liquid valve is 305 
psig. It would be necessary to add refrigerant to increase the liquid 
pressure to 320 psig.

 CAUTION

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR,
SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS
UNIT.

!

!

!

!

Summary of Contents for 19 SEER

Page 1: ...y charged with refrigerant for a nominal sized matching indoor coil plus 15 feet of field supplied lines SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay particular attention to the signal words DANGER WARNING or CAUTION DANGER indicates an imminently hazardous situation which if not av...

Page 2: ...oling operation below 35 F outdoor ambient temperature DO NOT modify the control System for these models to operate with any kind of Low Ambient kit 5 If this equipment is to be used in a low ambient outdoor application 55 F or lower a compressor crank case is heater accessory must be applied Please refer to UPGnet or price pages for the appropri ate Crank Case Heater for your model 6 The maximum ...

Page 3: ...QWHU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clearances 0 1 080 5 1 7 1 81 76 127 OHDUDQFH EHWZHHQ WZR XQLWV PD EH UHGXFHG WR PLQLPXP SURYLGHG WKH VHUYLFH DFFHVV FOHDUDQFH LV LQFUHDVHG WR PLQLPXP DQG WKH FOHDUDQFH RQ HDFK UHPDLQLQJ VLGH LV PDLQWDL...

Page 4: ...conditions may require direct wall mounted brackets to be used to locate and support the outdoor unit In these applications care must be taken to address unit base pan support structural integ rity safe access and serviceability as well as the possible sound and vibration transmission into the structure Wall mounting requires 3 mounting brackets and best served by a properly engineered solution Se...

Page 5: ... at the indoor coil 4 Braze the liquid line to the indoor coil liquid connection Nitrogen should be flowing through the indoor coil 5 Slide the grommet away from the vapor connection at the indoor coil Braze the vapor line to the indoor coil vapor connection After the connection has cooled slide the grommet back into original position 6 Protect the vapor valve with a wet rag and braze the vapor li...

Page 6: ...ngs See Figure 6 5 Slide the nut removed in step 3 over the supplied liquid line Place supplied Teflon washer from TXV kit in place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so liquid line aligns with hole in access panel Hand tighten the liq uid line and apply an additional 1 4 turn to seal 6 Install the TXV equalizer line onto the vapor line by han...

Page 7: ...gerant charge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow select the lowest possible speed tap measure the actual flow and adjust as necessary To measure actual air flow it is not an acceptable method to just check the jumper pin setting tables and to assume 0 5...

Page 8: ...rature and operate system for at least 10 15 minutes 2 Refer to the technical guide for the recommended indoor airflow and verify it is correct it should be 350 400 SCFM per ton 3 Measure and record the indoor wet bulb WB and the outdoor ambient dry bulb DB temperature 4 Using the charging chart located on the unit find the intersection of the indoor wet bulb and the outdoor dry bulb This is the r...

Page 9: ...ure to adjust charge in the unit Add or remove charge and adjust windows to maintain the desired temperature inside the tent TABLE 2 R 410A Saturation Properties TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG 45 130 60 170 75 217 90 274 105 341 46 132 61 173 76 221 91 278 106 345 47 135 62 176 77 224 92 282 107 350 48 137 63 179 78 228 93 2...

Page 10: ...pment the control box can slide down and swing open Considerations for running the electrical supply and power control wiring should be made to utilize this swing open feature for future service work You will not need to drop swing the box open for installation of the electrical supply and power wiring just account for the motion the box will have in the wire routing The complete connection diagra...

Page 11: ...volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and to the thermostat in the steps below 2 If utilizing the Demand Response or the Y2Lock feature a minimum of five thermostat wires will need to be ran to the outdoor unit from the indoor equipment If the features are not applied only four wires are needed 3 Trace the harness out where it ends in a large 12 pin Molex con nec...

Page 12: ... installation of the dehumidification control the HUM STAT jumper on the indoor variable speed air handler or furnace control board must be set to YES During cooling if the relative humidity in the space is higher than the desired set point of the dehumidification control the variable speed blower motor will operate at a lower speed until the dehumidification control is satisfied A 40 60 relative ...

Page 13: ...W RW 6HFRQG RU XOO 6WDJH RPSUHVVRU LUVW 6WDJH HDW 6HFRQG 6WDJH HDW LUVW 6WDJH RPSUHVVRU 7 2 67 9 5 63 851 21752 DQ 7 2 67 9 5 63 851 7KH 67 1 MXPSHU PXVW EH VHW WR 2 2 5HYHUVLQJ 9DOYH 0DOIXQFWLRQ LJKW 80 HKXPLGL FDWLRQ 7KH 7 3803 MXPSHU PXVW EH VHW WR 12 0RYH WKH 80 MXPSHU WR 6 LI D KXPLGLVWDW LV WR EH XVHG 7 2 67 5 21 7 21 5 67 3 21752 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 9ROW RPPRQ 5 9ROW RW 287 LU...

Page 14: ...HW WR 2 2 5HYHUVLQJ 9DOYH 0DOIXQFWLRQ LJKW 80 HKXPLGL FDWLRQ 7KH 7 3803 MXPSHU PXVW EH VHW WR 12 0RYH WKH 80 MXPSHU WR 6 LI D KXPLGLVWDW LV WR EH XVHG 7 2 67 5 21 7 21 5 67 3 21752 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 9ROW RPPRQ 5 9ROW RW 287 LUVW 6WDJH HDW 287 6HFRQG 6WDJH HDW 6LQJOH 6WDJH RPSUHVVRU 5 HPDQG 5HVSRQVH X LOLDU HDW 287 6HFRQG 6WDJH RPSUHVVRU 266 8 MXPSHU PXVW EH VHW WR 6 6HFRQG 6WDJH RP...

Page 15: ...R 6 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 02 8 7 1 851 21752 DQ 02 8 7 1 851 80 HKXPLGL FDWLRQ 2SHQ RQ XPLGLW 5LVH 0RGXODWLQJ HDW 0RYH 80 67 7 MXPSHU WR 6 LI KXPLGLVWDW LV WR EH XVHG 2 203 6LQJOH 6WDJH RPSUHVVRU 287 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 203 6HFRQG 6WDJH RPSUHVVRU 287 73803 MXPSHU PXVW EH VHW WR 12 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 9ROW RPPRQ 5 9ROW RW 287 LUVW 6WDJH HDW 287 6HFRQG...

Page 16: ...1 851 21752 DQ 02 8 7 1 851 80 HKXPLGL FDWLRQ 2SHQ RQ XPLGLW 5LVH 0RGXODWLQJ HDW 0RYH 80 67 7 MXPSHU WR 6 LI KXPLGLVWDW LV WR EH XVHG 2 203 6LQJOH 6WDJH RPSUHVVRU 287 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 203 6HFRQG 6WDJH RPSUHVVRU 287 73803 MXPSHU PXVW EH VHW WR 12 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 9ROW RPPRQ 5 9ROW RW 287 LUVW 6WDJH HDW 287 6HFRQG 6WDJH HDW 6LQJOH 6WDJH RPSUHVVRU 5 HPDQG 5HVSRQVH X ...

Page 17: ... 5HIHU WR GRFXPHQWDWLRQ IRU DQG HOHFWULF KHDW VWDJLQJ RSWLRQV RQQHFWLRQ RI WKH WHUPLQDO 9ROW FRPPRQ LV RSWLRQDO ZKHQ XVHG ZLWK EDWWHULHV 7KHUPRVWDW QVWDOOHU 6HWXS 6 VWHP 7 SH PXVW EH VHW WR HDW RRO 0XOWLVWDJH RQYHQWLRQDO WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH HDW 80 RQO RQ 6 7 68 3 E DQ 6 7 68 3 6 7 68 3 7 50267 7 7KLUG 6WDJH HDW 80 RQO RQ 6...

Page 18: ...HFWURQLF LU OHDQHU 80 287 9 RXW XPLGL HU 9 5 63 5 1 5 0RYH WKH 80 67 7 MXPSHU WR 6 LI KXPLGLVWDW LV WR EH XVHG 5HIHU WR GRFXPHQWDWLRQ IRU DQG HOHFWULF KHDW VWDJLQJ RSWLRQV WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 5 9ROW RW 7 2 67 5 21 7 21 5 67 3 21752 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 9ROW RPPRQ 5 9ROW RW 287 LUVW 6WDJH HDW 287 6HFRQG 6WDJH HDW 6LQJOH 6WDJH RPSUHVVRU 5 HPDQG ...

Page 19: ...active call less than two sec onds will display the current mode Pressing the PUSH BUTTON with no active call longer than six sec onds will display the current mode and tonnage AC HP is determined by the presence of the reversing valve ASCD Anti Short Cycle Delay After the tonnage is set a call may be given Y and or Y Y2 The control has a 5 minute anti short cycle delay It will count the minutes d...

Page 20: ... pressed during two stage anticipation mode with an active thermostat call The control will remove the forced second stage TABLE 6 Fault Code Description Required Condition LED 7 Segment Display 1 7 Segment Display 2 Control Response Control Fault Control Failure Control Failure Detected RED solid 0 0 Failure Operational Faults High pressure switch fault not in lockout yet HPS Opening RED solid 0 ...

Page 21: ...ceived in AC mode O signal received in AC mode 1 fault occurrence 2 RED flashes 1 8 Soft Lockout W signal received in AC mode W signal received in AC mode 1 fault occurrence 2 RED flashes 1 9 Soft Lockout W and O signal received in AC mode W and O signal received in AC mode 1 fault occurrence 2 RED flashes 2 0 Soft Lockout System previously configured as AC now HP No RV on configuration RV present...

Page 22: ...t be alarmed as this is normal operation If the conditions are on a break over point the motor could speed up and slow down until a more constant condition is met Under typical operation the motor will speed up the warmer it is outside and slow down the cooler it is outside to maintain highest efficiency and operating pressures as needed Charging of the equipment with the variable outdoor fan moto...

Page 23: ...MPR COMPRESSOR CONT CONTACTOR CCH COMPR CRANKCASE HEATER DR DEMAND RESPONSE DTS DISCHARGE TEMP SENSOR GND GROUND HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH SC START CAPACITOR SR START RELAY BLK BLACK BLU BLUE BLU PNK BLUE w PINK STRIPE BRN BROWN GRN GREEN GRN YEL GREEN w YELLOW STRIPE GRY GREY RED RED RED WHT RED w WHITE STRIPE WHT WHITE YEL YELLOW YEL BLK YELLOW w BLACK STRIPE YEL RED YELLO...

Page 24: ...5390862 UIM A 0318 24 Johnson Controls Unitary Products NOTES ...

Page 25: ...s L1 L2 Compressor amperes L1 L2 Measured voltage R and C outdoor unit control board Air Flow Setup Cooling Supply static inches of water column Supply air dry bulb temperature Return air dry bulb temperature Temperature drop A B C D Blower Type Set Up Outside air dry bulb temperature Return air wet bulb temperature Supply air wet bulb temperature Return static inches of water column Electrical Co...

Page 26: ...e Owner Education Comments and Additional Job Details Provide owner with the owner s manual Explain thermostat use and programming if applicable to owner Unit Operation and Cycle Test Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Job site has been c...

Reviews: