background image

898147-UUM-B-0713

8

Johnson Controls Unitary Products

 FIGURE 4:  

Indoor Unit Front Panel Indicators

72

HEA

T

INDICA

T

OR

COOL

INDICA

T

OR

TEMPERA

TURE*

RUN

DEHUMIDIFY

MODE

INFRARED

SIGNAL

RECEIVER

* The temperature readout (either
temperature setpoint or indoor ambient)
will be replaced by an error code if there
is a malfunction. If multiple errors are
detected, the display will alternate
between each error code.

NOTE:

No history is kept on past error codes.

TABLE 2: 

Problem

Possible Cause

Unit does not operate immediately after 
being restarted. 

Unit control initiates a 3 minute delay at the end of each cycle to protect the compressor from 
damage.

A whoosh or gurgling noise can be heard at 
the indoor unit. 

Sometimes, the refrigerant can be heard in the indoor coil when the outdoor unit starts or stops 
operation. This is not a malfunction.

Mist is coming out of the indoor unit during 
cooling operation. 

This sometimes happens when the indoor temperature and humidity are very high and the air is 
being cooled quickly. The mist will disappear as the indoor temperature and humidity are lowered. 

A creaking or popping noise can be heard 
when the unit starts or stops. 

The plastic components of the indoor units sometimes expand and contract when they are heated 
and cooled.

Unit is not operating. 

Are the TIMER ON and TIMER OFF features being used incorrectly?

Is power disconnected or has circuit breaker tripped.

Is power shut down?

System is not cooling (or heating) efficiently. 

Is temperature setting correct?

Are either the air inlet or air outlet blocked on the outdoor or indoor unit?

Is filter dirty?

Is fan at low speed?

Are windows and doors properly shut?

Wireless remote is not working. 

Is remote in direct line of sight with indoor unit infrared receiver? Has the remote been damaged? 

Remove remote control batteries for 30 seconds, then reinsert them. Replace batteries, if necessary.

Water is leaking from indoor unit. 

Indoor humidity level is very high and water is being blown from indoor coil. This will stop as humidity 
level is reduced. 

Water is leaking from condensate line at 
indoor unit. 

Check condensate line outside to make sure it is not obstructed. 

Check condensate line to make sure it has not been disconnected from indoor unit. 

Water is leaking from the outdoor unit. 

During operation in high humidity areas, condensate will form on cold outdoor refrigerant pipes. 

When heat pump is operating in defrost mode, ice will thaw from around outdoor coil and water will 
flow from the unit. 

Clicking noise heard inside. 

Sometimes, the sound of the outdoor unit fan or compressor relay can be transmitted in a way that 
makes it seem to be coming from the indoor unit. 

Indoor fan is not working. 

Heat pump units 

 In HEAT mode, a timed delay keeps indoor fan off for two minutes to prevent 

unheated air from being circulated by the indoor fan. 

Heat pump units 

 In HEAT mode, cold outdoor temperatures and high humidity cause frost to accu-

mulate on the outdoor unit. When this happens, the unit will enter a defrost cycle. The indoor fan is off 
during the 3 

 12 minute cycle. 

In DRY mode, indoor fan operation may be stopped to avoid delivery of moist air to the room. 
Do not adjust temperature setting. 

Summary of Contents for 16 SEER

Page 1: ...this manual before you start operating your new ductless system After reading this manual if you still need more information that may not have been covered in this manual please contact your HVAC cont...

Page 2: ...than R 22 Failure to use R 410A approved service equipment could result in equip ment explosion which could result in death or serious injury The refrigerant provided by the manufacturer complies with...

Page 3: ...y The unit will go into Auto Defrost mode and the heating will be discontinued for 8 to 10 minutes When the defrost cycle is complete the system will start running in heating mode While the outdoor un...

Page 4: ...UNIT ONE TO TWO ZONES 24 KBTU OUTDOOR UNIT TWO TO THREE ZONES 30 KBTU OUTDOOR UNIT TWO TO FOUR ZONES 42 KBTU OUTDOOR UNIT TWO TO FIVE ZONES AIR IN AIR OUT 1 2 3 8 4 5 7 6 1 Front Panel 2 Filter 3 Gui...

Page 5: ...ight with the indoor unit infrared receiver Make sure that there are no obstructions between the indoor unit receiver and the remote control when I FEEL feature is activated SWITCH FROM C TO F With sy...

Page 6: ...n AUTO mode 4 Keep pressing FAN button to select desired fan speed Fan speed selection is as fol low AUTO FAN LOW MID and HIGH 5 Press button to activate the swinging louver Press again to select a de...

Page 7: ...e healthy filter to the air filter as shown in Fig B Install the air filter properly as shown in Fig C and then close the panel CLEANING AND MAINTENANCE Remove the healthy filter and clean thoroughly...

Page 8: ...correct Are either the air inlet or air outlet blocked on the outdoor or indoor unit Is filter dirty Is fan at low speed Are windows and doors properly shut Wireless remote is not working Is remote in...

Page 9: ...anty shall cover the heat exchanger primary and or secondary if applicable only if 1 The product has not been operated with an input rate in excess of the rating plate attached to the product 2 The pr...

Page 10: ...n of the water circuit by foreign material or like causes 13 Damages caused by improper parts components or accessories not suitable for use in or with the unit For a list of parts that are known to b...

Reviews: