background image

898147-UUM-B-0713

Johnson Controls Unitary Products

3

DUCTLESS SYSTEM OPERATION

MUTI-SPLITS APPLICATION ONLY

In a multi-split application, the operating mode is determined by the
zone that initiates the first demand for heating or cooling. If the system
is energized and a heating demand has been initiated by zone 1, an
error code (E7) will be displayed of the front panel of the indoor unit of
any zone trying to initiate a cooling demand. The zone 1 remote (and
remotes for other zones calling for heating) must be powered off in
order to allow the system operating mode to switch to the cooling mode.
Once the zone initiates the cooling demand, the mode will have to be
reset in the same way to allow a heating demand in another zone. This
situation occurs only when there are very different requirements in two
or more zones in the system.

SINGLE SPLIT AND MULTI-SPLITS APPLICATIONS

COOLING MODE OPERATION

1.

Cooling Mode Operation Principles -

 In the cooling mode, the

indoor coil absorbs the heat from the room and transfers it to the
outdoor coil where it is discharged. The system cooling capacity is
affected by the outdoor ambient temperature. The indoor fan oper-
ates continuously in cooling mode even when the cooling setpoint
temperature is reached. The indoor unit swing louver is fixed in an
upward position. The cooling operating range of the outdoor unit is
typically from 5°F (-15°C) to 115°F (46°C) for small capacity sys-
tems (9K & 12K) and 14°F (-10°C) to 115°F (46°C) for large capac-
ity systems (18+K).

2.

Anti-Freezing Protection in Cooling Mode -

 If the unit is running

in cooling mode and frost starts forming on the indoor coil, the out-
door unit compressor will stop to protect your ductless system.

HEATING OPERATION

1.

Heating Operation Principles -

 The refrigerant flow is reversed

during the heating cycle. The outdoor coil absorbs the heat from
outside and transfers it to the indoor coil where it is discharged into
the living space. The system heating capacity is also affected by
the outdoor ambient temperature. In heating mode, the indoor
blower will continue to operate for 60 seconds after the outdoor unit
shuts off. The indoor unit swing louver is fixed in a downward posi-
tion. The heating operating range of the outdoor unit is from 19 °F (-
7°C) to 75°F (24°C). In extreme low temperature conditions, it may
be necessary to supplement heating using other means such as
space heater, fireplace, etc.

2.

Auto Defrost -

 When the outdoor temperature is low and/or with

high humidity, frost may form on the outdoor coil, reducing the abil-
ity of the unit to transfer energy. The unit will go into Auto Defrost
mode and the heating will be discontinued for 8 to 10 minutes.
When the defrost cycle is complete, the system will start running in
heating mode. While the outdoor unit is in defrost mode, the follow-
ing occur:

• The fan motors of the indoor and outdoor units will stop running.
• The indoor unit indicator flashes, and moisture may flow from the

outdoor unit and steam may be observed.

3.

Cold Air Prevention - Hot Heat Pump -

 In heating mode, if the

indoor coil has not achieved a certain temperature, the indoor fan
will not operate for up to 3 minutes. This may occur during:

• Initial start-up of a heating cycle
• Immediately after completion of an Auto mode operation
• Heating under extremely low indoor temperatures

AUTO MODE OPERATION

When AUTO mode is selected, the setpoint temperatures in heating
and cooling modes are predetermined. When AUTO mode is activated,
the remote control temperature setpoint and fan operation cannot be
adjusted.

1.

AUTO Mode - Cooling Operation -

 If the indoor ambient tempera-

ture is greater than 77°F (25°C), the ductless system will operate in
cooling mode and will continue to run until the indoor ambient tem-
perature reaches 75°F (24°C). At this point, the outdoor unit's com-
pressor and outdoor fan will operate for another 60 seconds, then
they will both turn off. The indoor fan will run continuously at a
speed determined by the indoor ambient temperature. When the
system is in AUTO mode and in cooling operation, the indoor unit
swinging louver is fixed in an upward position. 

2.

Auto Mode - Heating Operation (heat pump only) -

 If the indoor

ambient temperature is less than 68°F (20°C), the system will oper-
ate in heating mode and will continue to run until the indoor ambient
temperature reaches 69°F (21°C). At this point, the outdoor unit's
compressor and outdoor fan will operate for another 60 seconds,
then they will both turn off. The indoor fan will run continuously at a
speed determined by the indoor ambient temperature. When the
system is in AUTO mode and in heating operation, the indoor unit
swing louver is fixed in a downward position.

FAN MODE OPERATION

When the system is set to operate in FAN mode, the indoor fan runs
continuously in AUTO, low, medium or high speed. The outdoor unit is
off. In AUTO fan mode, the fan speed is determined by the indoor ambi-
ent air temperature.

DRY MODE OPERATION

When the system is set to operate in DRY mode, the indoor fan runs
continuously at low speed to maximize indoor air moisture removal.

TYPICAL INSTALLATION

SINGLE SPLIT

 FIGURE 1: 

Single-Split Indoor

ON/OFF

* To be provided at field

INDOOR UNIT

OUTDOOR UNIT

AIR IN

AIR IN

AIR OUT

AIR OUT

1

2

3

8

4

5

7

6

2

1. Power Cable*

2. Remote Control

3. Front Panel

4. Filter

5. Guide Louver

6. Wall Pipe

7 Bind Tape

8. Drainage Pipe

Summary of Contents for 16 SEER

Page 1: ...this manual before you start operating your new ductless system After reading this manual if you still need more information that may not have been covered in this manual please contact your HVAC cont...

Page 2: ...than R 22 Failure to use R 410A approved service equipment could result in equip ment explosion which could result in death or serious injury The refrigerant provided by the manufacturer complies with...

Page 3: ...y The unit will go into Auto Defrost mode and the heating will be discontinued for 8 to 10 minutes When the defrost cycle is complete the system will start running in heating mode While the outdoor un...

Page 4: ...UNIT ONE TO TWO ZONES 24 KBTU OUTDOOR UNIT TWO TO THREE ZONES 30 KBTU OUTDOOR UNIT TWO TO FOUR ZONES 42 KBTU OUTDOOR UNIT TWO TO FIVE ZONES AIR IN AIR OUT 1 2 3 8 4 5 7 6 1 Front Panel 2 Filter 3 Gui...

Page 5: ...ight with the indoor unit infrared receiver Make sure that there are no obstructions between the indoor unit receiver and the remote control when I FEEL feature is activated SWITCH FROM C TO F With sy...

Page 6: ...n AUTO mode 4 Keep pressing FAN button to select desired fan speed Fan speed selection is as fol low AUTO FAN LOW MID and HIGH 5 Press button to activate the swinging louver Press again to select a de...

Page 7: ...e healthy filter to the air filter as shown in Fig B Install the air filter properly as shown in Fig C and then close the panel CLEANING AND MAINTENANCE Remove the healthy filter and clean thoroughly...

Page 8: ...correct Are either the air inlet or air outlet blocked on the outdoor or indoor unit Is filter dirty Is fan at low speed Are windows and doors properly shut Wireless remote is not working Is remote in...

Page 9: ...anty shall cover the heat exchanger primary and or secondary if applicable only if 1 The product has not been operated with an input rate in excess of the rating plate attached to the product 2 The pr...

Page 10: ...n of the water circuit by foreign material or like causes 13 Damages caused by improper parts components or accessories not suitable for use in or with the unit For a list of parts that are known to b...

Reviews: