background image

5121495-UIM-D-0516

2

Johnson Controls Unitary Products

INSPECTION

As soon as a unit is received, it should be inspected for possible dam-

age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.

Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle the POE type oils, and the higher
pressures of R-410A.

Manifold sets should be high side and low side with low side
retard.

All hoses must have a 700 psig service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.

Do not use an R-22 TXV.

LIMITATIONS

The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:

1.

Limitations for the indoor unit, coil, and appropriate accessories
must also be observed.

2.

The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.

3.

The maximum and minimum conditions for operation must be
observed to ensure a system that will give maximum performance
and service life.

4.

The unit should not be operated in cooling mode at outdoor tem-
peratures below 50°F without an approved low ambient operation
accessory kit installed.

5.

The maximum allowable line length for this product is 80 feet. To
install more than the maximum allowable line length, consult the
Piping Application Guide (P/N 247077).

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, air discharge, and service access. See Figure 1.

If the unit is to be installed on a hot sun exposed roof or a paved ground
area that is seasonally hot, the unit should be raised sufficiently above
the roof or ground to avoid taking the accumulated layer of hot air into
the outdoor unit.

If the system is being installed during seasonally cold weather of 55°F
or below, the preferred method is to weigh in the charge. For charging
or checking the system charge at 55°F or below, refer to the “Optional
Cold Weather Charging” procedures near the end of SECTION VI:
SYSTEM CHARGE. There is an “Optional Cold Weather Charging”
accessory kit to prevent the outdoor unit from taking in cold air below
55°F. The kit part number can be found in the list of accessory kits on
the UPGNET web site.

Provide adequate structural support for the unit.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-410A unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. The following steps should be performed in order to insure
proper system operation and performance. Line-set change out is also
recommended.

1.

Change-out of the indoor coil to an approved R-410A coil/ con-
densing unit combination with the appropriate metering device.

2.

Change-out of the line-set when replacing an R-22 unit with an
R410-A unit is highly recommended to reduce cross-contamina-
tion of oils and refrigerants.

3.

If change-out of the line set is not practical, then the following pre-
cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.

Determine if there are any low spots which might be serving as oil
traps.

Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possible.

Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation.

4.

If the outdoor unit is being replaced due to a compressor burnout,
then installation of a 100% activated alumina suction-line filter
drier in the suction-line is required, in addition to the factory
installed bi-flow liquid-line drier. Operate the system for 10 hours.
Monitor the suction drier pressure drop. If the pressure drop
exceeds 3 psig, replace both the suction-line and liquid-line driers.

After a total of 10 hours run time where the suction-line pressure

drop has not exceeded 3 psig, replace the liquid line drier, and
remove the suction-line drier. Never leave a suction-line drier in
the system longer than 50 hours of run time.

TABLE 1: 

Maximum / Minimum Operating Limit Conditions

AIR TEMPERATURE AT 

OUTDOOR COIL, °F

AIR TEMPERATURE AT 

INDOOR COIL, °F

Min.

Max.

Min.

Max.

DB 

Cool

DB 

Heat

DB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

50° F

-20° F

125° F

75° F

57° F

50° F

72° F

80° F

Operation below this temperature is permissible for a short period of time, 
during morning warm-up.

NOTICE

For multiple unit installations, units must be spaced a minimum of
24” (61 cm) apart (coil face to coil face).

Summary of Contents for 14 SEER-YHE SERIES

Page 1: ...ng indoor coils can be used with a thermostatic expansion valve TXV Refer to the Tabular Data Sheet or to the Technical Guide for the proper selection SECTION II SAFETY This is a safety alert symbol W...

Page 2: ...e preferred method is to weigh in the charge For charging or checking the system charge at 55 F or below refer to the Optional Cold Weather Charging procedures near the end of SECTION VI SYSTEM CHARGE...

Page 3: ...ess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base...

Page 4: ...internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also...

Page 5: ...ischarged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep teflon washer in place and dis...

Page 6: ...gerant charge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow sele...

Page 7: ...control box can swing open by removing the screw from the center of each side of the control box and allowing the control box to lower an inch or so into a pivotal position The control box can then s...

Page 8: ...disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figures 9 10 5 Install the proper size time delay fuses or cir...

Page 9: ...www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furna...

Page 10: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 3 TES...

Page 11: ...arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulat...

Page 12: ...cur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal...

Page 13: ...h code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the...

Page 14: ...AL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUS...

Page 15: ...5121495 UIM D 0516 Johnson Controls Unitary Products 15 NOTES...

Page 16: ...plicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connecte...

Page 17: ...mp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board instal...

Page 18: ...des 5121495 UIM C 0316 York International Corp 5005 York Drive Norman OK 73069 Explain operation of system to equipment owner Explain the importance of regular filter replacement and equipment mainten...

Reviews: