background image

5121495-UIM-D-0516

Johnson Controls Unitary Products

11

FAULT CODE DISPLAY

The control shall provide status codes using the LED. Status codes
indicate the state of operation of the unit but do not represent a fault.
The table below describes the LED displays during status codes. Status
codes will not be displayed when a fault code is present.

The control shall provide fault codes using the Status LED. The table
below describes the LED displays during fault codes. Unless otherwise
specified, the control shall provide flashes that are a 1/3 second on and
1/3 second off for fault codes. The control shall only display a single
fault code on the LED. The control shall display the fault code on the
LED repeatedly with a 2 second off period between repetitions of the
fault code. If multiple fault codes are present at the same time, the LED
shall display only the most recent fault. 

The table below shows a number that represents the number of flashes
for the specified code. For instance, a flash code entry of 3 indicates
that the control will energize the output for three 1/3 second on, 1/3 sec-
ond off flashes, wait two seconds, then energize the output for three
more 1/3 second on, 1/3 second off flashes and repeat.

Demand Defrost

The control maintains proper airflow through the outdoor coil during
heating operation by melting frost and ice that may form on the coil.
Frost may accumulate unevenly in different sections of the coil because
of the arrangement of the refrigeration circuit within the coil. The control
may initiate a defrost cycle even when the coil is not completely cov-
ered with frost. This is normal operation.

The control regulates the defrost operation of the heat pump based on
accumulated compressor run time, outdoor coil temperature, and out-
door ambient temperature. The control will cause the heat pump unit to
operate in the normal heating mode until it determines that a defrost
cycle is needed.

All defrost timings are based on accumulated compressor run time.

 FIGURE 13: 

Demand Defrost Control Module

$

'()5267&859(

7(67

& 5

2 < : :RXW

+36

/36

59

&0

&2,/

$0%

67$786/('

TABLE 5: 

Status Code Display

No power to the control

No Faults active 
Nothing energized

OFF

Compressor Operation 

Active 

No Faults active 
M energized

ON

Control normal operation –
no call for compressor

No faults active 
Y not present

2s ON/2s OFF

Control normal operation –
in ASCD period

No faults active, 
Y present, ASCD 
timer not expired

0.1 sec ON/0.1 sec OFF

TABLE 6: 

Status

Description

STATUS LED

High -pressure switch fault (not in lockout yet)

2 Flashes

System in high-pressure switch lockout 
(last mode of operation was normal compressor 
operation)

3 Flashes

System in high-pressure switch lockout 
(last mode of operation was defrost)

4 Flashes

System in low-pressure switch lockout 
(last mode of operation was normal compressor 
operation)

5 Flashes

Low Voltage (<19.2VAC) preventing further 
relay outputs for > 2 seconds

6 Flashes

Low Voltage (<16VAC) stopped current relay 
outputs for > 2 seconds

7 Flashes

Coil sensor failure (Open or Shorted)

8 Flashes

Outdoor ambient sensor failure (Open or Shorted)

9 Flashes

Control Failure

10 Flashes

Summary of Contents for 14 SEER-YHE SERIES

Page 1: ...ng indoor coils can be used with a thermostatic expansion valve TXV Refer to the Tabular Data Sheet or to the Technical Guide for the proper selection SECTION II SAFETY This is a safety alert symbol W...

Page 2: ...e preferred method is to weigh in the charge For charging or checking the system charge at 55 F or below refer to the Optional Cold Weather Charging procedures near the end of SECTION VI SYSTEM CHARGE...

Page 3: ...ess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base...

Page 4: ...internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also...

Page 5: ...ischarged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep teflon washer in place and dis...

Page 6: ...gerant charge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow sele...

Page 7: ...control box can swing open by removing the screw from the center of each side of the control box and allowing the control box to lower an inch or so into a pivotal position The control box can then s...

Page 8: ...disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figures 9 10 5 Install the proper size time delay fuses or cir...

Page 9: ...www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furna...

Page 10: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 3 TES...

Page 11: ...arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulat...

Page 12: ...cur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal...

Page 13: ...h code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the...

Page 14: ...AL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUS...

Page 15: ...5121495 UIM D 0516 Johnson Controls Unitary Products 15 NOTES...

Page 16: ...plicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connecte...

Page 17: ...mp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board instal...

Page 18: ...des 5121495 UIM C 0316 York International Corp 5005 York Drive Norman OK 73069 Explain operation of system to equipment owner Explain the importance of regular filter replacement and equipment mainten...

Reviews: