background image

5121495-UIM-D-0516

16

Johnson Controls Unitary Products

SECTION XII: START UP SHEET

Heat Pump and Supplementary Heat Start-Up Sheet 

 Proper start-up is critical to customer comfort and equipment longevity

  

 

  

  

  
  
  
  
  

  

  
  
  
  
  

  

  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

  

  
  
  
  
  
  
  
  
 

Name

Address

City

State or Province

Zip or Postal Code

Indoor Unit Model #

Indoor Unit Serial #

Indoor Coil Model #

Indoor Coil Serial #

Upflow

Downflow

Horizontal Left

Horizontal Right

Unit is level

Venting system properly sized, within the limitations of the charts in the installation instructions.

Condensate drain for indoor coil properly connected

Filter Type

Intake Size

Exhaust Size

# of 90 Degree Ells

# 0f 45 Degree Ells

Length 

Length 

# 0f 45 Degree Ells

# of 90 Degree Ells

Polarity is correct (120vac indoor units) black is L1 (hot), white is N (neutral)

Ground wire is connected

Indoor unit (volts AC)

Low voltage values: "R" and "C" at Indoor unit control board (volts AC)

Thermostat Type

Other System Equipment and Accessories

Owner Information

Equipment Data

Venting (if applicable)

Electrical: Line Voltage

 

Outdoor Unit Model #

Outdoor Unit Serial #

Filter, Thermostat, Accessories

Filter Location(s)

Connections -- Per Installation Instructions and Local Codes 

Gas piping is connected (if applicable)

Supply plenum and return ducts are connected and sealed

Filter Size

Vent system is connected (if applicable)

Thermostat wiring complete

Heat anticipator is set to the recommended value listed in the Installation Instructions

Electrical: Low Voltage

 

Technician Performing Start-Up

Installing Contractor Name

Start-Up Date

Condensate drain for furnace (if applicable) 

Refrigerant piping complete and leak tested

Outdoor unit (volts AC)

Overcurrent Protection Breaker / Fuses Amperes

"R" and "C" Outdoor unit control board (volts AC)

Supplementary Heating Set-Up

 

Natural Gas

LP Gas (Requires LP Conversion Kit)

Electric Air Handler

LP Gas Conversion Kit Part # Used

LP Kit Installed By

Inlet Gas Pressure (in. w.c.")

Calculated input in btuh - clock the gas meter (Nat Gas Only) 

Manifold Gas Pressure (in. w.c.")

Heating Type

Heat anticipator  

recommended value

Electric Heat Kit Part # (if applicable)

KW installed

 

Continued on next Page 

Rated BTU/H (furnaces)

Print Form

Reset Form

Summary of Contents for 14 SEER-YHE SERIES

Page 1: ...ng indoor coils can be used with a thermostatic expansion valve TXV Refer to the Tabular Data Sheet or to the Technical Guide for the proper selection SECTION II SAFETY This is a safety alert symbol W...

Page 2: ...e preferred method is to weigh in the charge For charging or checking the system charge at 55 F or below refer to the Optional Cold Weather Charging procedures near the end of SECTION VI SYSTEM CHARGE...

Page 3: ...ess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base...

Page 4: ...internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also...

Page 5: ...ischarged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep teflon washer in place and dis...

Page 6: ...gerant charge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow sele...

Page 7: ...control box can swing open by removing the screw from the center of each side of the control box and allowing the control box to lower an inch or so into a pivotal position The control box can then s...

Page 8: ...disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figures 9 10 5 Install the proper size time delay fuses or cir...

Page 9: ...www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furna...

Page 10: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 3 TES...

Page 11: ...arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulat...

Page 12: ...cur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal...

Page 13: ...h code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the...

Page 14: ...AL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUS...

Page 15: ...5121495 UIM D 0516 Johnson Controls Unitary Products 15 NOTES...

Page 16: ...plicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connecte...

Page 17: ...mp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board instal...

Page 18: ...des 5121495 UIM C 0316 York International Corp 5005 York Drive Norman OK 73069 Explain operation of system to equipment owner Explain the importance of regular filter replacement and equipment mainten...

Reviews: