background image

246723-YTG-J-1006

2

Unitary Products Group

All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request.

PHYSICAL AND ELECTRICAL DATA

MODEL

CZB01811

CZB02411

CZB03011

CZB03611

CZB04211

CZB04811

CZB06011

Unit Supply Voltage

208-230V, 1

φ,

 60Hz

Normal Voltage Range 

1

187  to 252

Minimum Circuit Ampacity

13.3

16.5

18.9

22.3

28.7

27.9

34.4

Max. Overcurrent Device Amps 

2

20

25

30

35

50

45

60

Min. Overcurrent Device Amps 

3

15

20

20

25

30

30

35

Compressor Type 

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Compressor Amps

Rated Load

10.3

14.3

16.4

16.6

21.8

21.1

26.3

Locked Rotor

51

60

73

88

105

113

150

Crankcase Heater

No

No

No

No

No

No

No

Fan Motor Amps

Rated Load

0.5

0.5

0.5

1.5

1.5

1.5

1.5

Fan Diameter Inches

22

22

22

22

22

22

22

Fan Motor

Rated HP

1/15

1/15

1/15

1/4

1/4

1/4

1/4

Nominal RPM

850

850

850

850

850

850

850

Nominal CFM

2100

2,250

2,300

3,200

3,250

3,500

3,500

Coil

Face Area Sq. Ft.

14.86

14.86

17.15

17.15

20.58

20.58

20.58

Rows  Deep

1

1

1

1

1

1

2

Fins / Inch

22

22

22

22

22

22

22

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

3/4

7/8

7/8

7/8

Unit Charge (Lbs. - Oz.) 

4

5-13

6-4

7-4

6-4

8-13

8-12

13-9

Charge Per Foot, Oz.

0.62

0.62

0.62

0.62

0.67

0.67

0.67

Operating Weight Lbs.

165

170

190

190

205

215

260

1

Rated in accordance with ARI Standard 110, utilization range “A”.

2

Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3

Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4

The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

VAPOR

LIQUID

2-3/8

3-1/8

6-1/2

C

A

B

DIMENSIONS

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

B

C

Liquid

Vapor

018

29-1/2

37

31

3/8”

3/4”

024

29-1/2

37

31

030

33-1/2

37

31

036

33-1/2

37

31

042

39-1/2

37

31

7/8”

048

39-1/2

37

31

060

39-1/2

37

31

Summary of Contents for 13 SEER - R410A CZB018 THRU 060

Page 1: ...ressures by an internal pressure relief valve and factory installed high and low pressure controls Additional protection against moisture and debris is provided by factory installed liquid line filter...

Page 2: ...Area Sq Ft 14 86 14 86 17 15 17 15 20 58 20 58 20 58 Rows Deep 1 1 1 1 1 1 2 Fins Inch 22 22 22 22 22 22 22 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Inst...

Page 3: ...FC MC PC UC36C3X 3 3 FC MC PC UC42B3X 3 FC MC PC UC42C3X 3 FC MC PC UC48C3X 6 FC MC PC UC48D3X 6 FC PC UC60C3X 12 4 FC MC PC UC60D3X 12 4 MC61D3X 4 HC18A3X 5 HC30A3X 6 HC36B3X 3 3 HC42C3X HC60D3X 6 1...

Page 4: ...3 G1FA G1UA048S17 3 3 G1FA G1UA048S21 3 3 G1FA G1UA060S21 24 6 12 4 F RP024 F FP024 5 F RP030 F FP030 6 3 F RP036 F FP036 3 3 F RP042 F FP042 3 F RP045 F FP045 6 F FP048 6 F FP060 F FV060 12 4 G4FD02...

Page 5: ...00 36 0 26 5 13 00 11 00 CZB04211 MA16C 5 8 10 15 20 21 FC MC48C 1400 41 0 30 2 13 00 11 00 MA14D 5 8 10 15 19 24 FC MC48D 1400 41 0 30 2 13 00 11 00 MA16C 5 8 10 15 20 21 G FD048H21 1400 41 0 30 2 13...

Page 6: ...12 1 14 00 11 50 CZB02411 AV24 2 5 8 10 17 800 23 0 16 7 14 00 11 50 CZB03011 AV36 5 8 10 15 18 17 1000 30 0 21 9 14 00 11 50 CZB03611 AV36 5 8 10 15 18 17 1200 36 0 26 5 14 00 11 50 CZB04211 AV SV48...

Page 7: ...36H17 1000 30 0 21 9 13 00 11 00 21 G FD036H21 1000 30 0 21 9 13 00 11 00 21 G FD042H21 1000 30 0 21 9 13 00 11 00 17 G FD046H17 1000 30 0 21 9 13 00 11 00 17 HC36 950 30 0 21 9 13 00 11 00 HD36 1000...

Page 8: ...MC PC30B 17 1000 30 0 21 9 13 50 11 00 P C V 9 B12 FC MC PC30B 17 1000 30 0 21 9 13 50 11 00 PV8 A12 FC MC PC36A 14 1000 30 0 22 3 14 00 11 50 PV9 A12 FC MC PC36A 14 1000 30 0 22 3 14 00 11 50 PV8 B16...

Page 9: ...48 0 36 1 13 05 11 00 PV9 D20 HD60 24 1600 48 0 36 1 13 25 11 00 PV9 C20 MC60D 21 1600 48 0 36 1 13 05 11 00 CZB06011 PV9 D20 FC MC PC60D 24 1620 55 0 39 3 13 25 11 00 PV8 C20 FC PC60C 21 1730 55 5 39...

Page 10: ...rmo stat 1H 1C auto manual change over electronic programmable deluxe 7 day thermostat 1H 1C auto manual change over electronic programmable For the most current accessory information refer to the pri...

Page 11: ...6 1 6 1 6 1 6 1 6 1 6 1 6 1 6 1 6 1 6 1 5 105 T C 12 7 14 6 13 8 15 6 16 8 14 3 15 9 15 0 16 9 17 9 15 8 17 3 16 2 18 1 19 0 S C 12 7 11 8 9 5 9 5 7 1 14 2 13 9 11 3 11 3 8 3 15 7 15 9 13 1 13 1 9 4 K...

Page 12: ...3 0 18 7 19 1 14 3 K W 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 0 2 1 2 0 2 0 105 T C 17 4 18 3 18 0 20 4 23 2 19 2 19 8 18 9 21 2 23 8 21 0 21 4 19 7 22 0 24 5 S C 17 2 15 7 13 2 13 4 10 9 18 9...

Page 13: ...21 0 20 4 16 3 27 2 27 1 23 0 22 5 18 1 K W 2 9 3 6 2 9 3 0 3 0 2 9 3 2 2 9 3 0 3 0 2 9 2 9 2 9 3 0 3 0 115 T C 21 6 21 9 22 9 23 6 26 7 23 4 23 5 23 6 25 3 27 9 25 1 24 7 24 4 27 0 29 2 S C 22 4 22 9...

Page 14: ...0 0 29 8 25 0 25 5 19 8 31 1 31 2 26 6 27 1 21 0 K W 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 115 T C 29 0 29 1 27 6 31 0 32 7 30 1 30 0 28 0 31 5 33 0 31 2 30 9 28 4 32 1 33 2 S C...

Page 15: ...6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 6 3 7 105 T C 33 5 34 7 34 5 37 5 42 0 35 0 35 7 35 3 38 4 42 8 36 5 36 7 36 2 39 3 43 6 S C 33 4 32 5 27 5 26 9 20 8 34 9 34 8 29 7 29 1 22 2 36 5...

Page 16: ...39 3 40 5 33 3 34 2 26 7 41 0 42 3 35 4 36 5 28 1 42 7 44 2 37 5 38 8 29 5 K W 4 2 4 2 4 1 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 3 4 2 105 T C 41 0 42 0 39 5 44 8 48 2 42 6 43 1 40 2 45 4 48 2 44...

Page 17: ...9 K W 5 0 5 0 4 9 5 1 5 2 5 0 5 0 5 0 5 1 5 2 5 0 5 0 5 0 5 1 5 2 105 T C 46 4 47 7 46 5 52 4 55 6 47 1 48 9 48 1 53 4 56 4 47 8 50 1 49 6 54 4 57 2 S C 36 9 44 6 40 7 37 2 27 8 39 0 47 1 41 7 39 5 29...

Page 18: ...246723 YTG J 1006 18 Unitary Products Group NOTES...

Page 19: ...246723 YTG J 1006 Unitary Products Group 19 NOTES...

Page 20: ...o change without notice Printed in U S A 246723 YTG J 1006 Copyright by York International JCI 2006 All rights reserved Supersedes 246723 YTG H 0906 Unitary 5005 Norman Products York OK Group Drive 73...

Reviews: