246723-YTG-J-1006

14

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

CZB03611

INDOOR COIL MODEL NO.

G2FD036S17

CONDENSER 

ENTERING AIR 

TEMPERATURE

ID CFM

1050

1200

1350

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

32.7

33.4

31.9

34.6

38.3

34.4

34.2

32.1

35.6

38.5

36.1

34.9

32.4

36.6

38.7

S.C.

30.7

30.6

24.4

24.3

19.2

31.9

32.4

26.2

33.4

20.7

33.1

34.1

28.0

42.5

22.1

K.W.

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

75

T.C.

35.5

36.2

35.4

38.9

41.7

36.8

37.3

36.0

39.8

42.2

38.1

38.4

36.6

40.6

42.6

S.C.

33.7

31.3

26.3

26.3

21.1

35.1

33.5

28.0

20.8

22.1

36.6

35.6

29.8

15.4

23.2

K.W.

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

85

T.C.

34.1

34.8

33.6

36.7

40.0

35.6

35.7

34.0

37.7

40.3

37.1

36.6

34.5

38.6

40.7

S.C.

32.2

31.0

25.3

25.3

20.1

33.5

32.9

27.1

27.1

21.4

34.8

34.9

28.9

29.0

22.7

K.W.

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

95

T.C.

32.4

32.9

31.6

34.8

37.5

33.8

33.8

32.0

35.6

37.8

35.1

34.7

32.4

36.4

38.2

S.C.

30.5

29.7

24.4

24.6

19.4

31.8

31.4

26.1

26.3

20.6

33.0

33.1

27.8

28.0

21.8

K.W.

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

3.2

105

T.C.

30.7

31.0

29.5

32.9

35.1

31.9

31.9

30.0

33.5

35.4

33.1

32.8

30.4

34.2

35.6

S.C.

28.9

28.3

23.5

23.8

18.6

30.0

29.8

25.0

25.5

19.8

31.1

31.2

26.6

27.1

21.0

K.W.

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

115

T.C.

29.0

29.1

27.6

31.0

32.7

30.1

30.0

28.0

31.5

33.0

31.2

30.9

28.4

32.1

33.2

S.C.

27.3

27.0

22.6

23.0

17.8

28.3

28.2

24.0

24.6

19.0

29.3

29.5

25.5

26.2

20.2

K.W.

4.1

4.1

4.1

4.1

4.0

4.1

4.1

4.1

4.0

4.0

4.1

4.1

4.1

4.0

4.1

125

T.C.

27.4

27.2

25.6

29.1

30.3

28.3

28.2

26.0

29.5

30.5

29.3

29.1

26.4

29.9

30.8

S.C.

25.7

25.7

21.7

22.3

17.1

26.6

26.7

23.0

23.8

18.2

27.5

27.7

24.4

25.3

19.3

K.W.

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

MA12B

FC/MC36B

1.00

1.00

1.00

MA12B

FC/MC42B

1.01

1.00

1.00

MA12B

G*FD046H17

1.01

1.00

1.00

MA14D

G*FD048H24

1.01

1.00

1.00

MV12B

MC36B

1.01

1.00

1.00

MV12B

MC42B

1.01

1.01

1.00

AHP36

1.01

1.00

1.00

AHP42

1.01

1.00

1.00

AV36

1.01

1.00

0.95

F*FP036

1.01

1.01

1.00

F*FP042

1.02

1.01

1.00

FC/MC/PC/UC36

1.00

1.00

1.00

FC/MC/PC/UC42

1.01

1.00

1.00

G*FA048S17

1.01

1.00

1.00

G*FA048S21

1.01

1.00

1.00

G*FD036H21

1.01

1.00

1.00

G*FD042H21

1.01

1.00

1.00

G*FD046H17

1.01

1.00

1.00

G*FD048H21,24

1.01

1.00

1.00

HC36

1.01

1.00

1.00

HD36

1.00

1.00

1.00

Variable Speed 
Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC36A

0.98

0.98

1.00

PV9*A12

FC/MC/PC36A

1.00

1.00

1.00

PV8*B16

FC/MC/PC36B

1.01

1.00

1.00

PV9*B12

FC/MC/PC36B

1.00

1.00

1.00

PV8*C16

FC/MC/PC36C

1.01

1.00

1.00

PV8*C20

FC/MC/PC36C

1.01

1.00

1.00

PV9*C16

FC/MC/PC36C

1.00

1.00

1.00

PV9*C20

FC/MC/PC36C

1.00

1.00

1.00

PV8*B16

FC/MC/PC42B

1.03

1.03

1.00

PV9*B12

FC/MC/PC42B

1.01

1.01

1.00

PV8*C16

FC/MC/PC42C

1.03

1.03

1.00

PV8*C20

FC/MC/PC42C

1.03

1.03

1.00

PV8*B16

HC36

1.01

1.00

1.00

PV9*B12

HC36

1.01

1.00

1.00

PV8*C16

HD36

1.01

1.00

1.00

PV9*C16

HD36

1.01

1.00

1.00

PV9*C20

HD36

1.01

1.00

1.00

Summary of Contents for 13 SEER - R410A CZB018 THRU 060

Page 1: ...ressures by an internal pressure relief valve and factory installed high and low pressure controls Additional protection against moisture and debris is provided by factory installed liquid line filter...

Page 2: ...Area Sq Ft 14 86 14 86 17 15 17 15 20 58 20 58 20 58 Rows Deep 1 1 1 1 1 1 2 Fins Inch 22 22 22 22 22 22 22 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Inst...

Page 3: ...FC MC PC UC36C3X 3 3 FC MC PC UC42B3X 3 FC MC PC UC42C3X 3 FC MC PC UC48C3X 6 FC MC PC UC48D3X 6 FC PC UC60C3X 12 4 FC MC PC UC60D3X 12 4 MC61D3X 4 HC18A3X 5 HC30A3X 6 HC36B3X 3 3 HC42C3X HC60D3X 6 1...

Page 4: ...3 G1FA G1UA048S17 3 3 G1FA G1UA048S21 3 3 G1FA G1UA060S21 24 6 12 4 F RP024 F FP024 5 F RP030 F FP030 6 3 F RP036 F FP036 3 3 F RP042 F FP042 3 F RP045 F FP045 6 F FP048 6 F FP060 F FV060 12 4 G4FD02...

Page 5: ...00 36 0 26 5 13 00 11 00 CZB04211 MA16C 5 8 10 15 20 21 FC MC48C 1400 41 0 30 2 13 00 11 00 MA14D 5 8 10 15 19 24 FC MC48D 1400 41 0 30 2 13 00 11 00 MA16C 5 8 10 15 20 21 G FD048H21 1400 41 0 30 2 13...

Page 6: ...12 1 14 00 11 50 CZB02411 AV24 2 5 8 10 17 800 23 0 16 7 14 00 11 50 CZB03011 AV36 5 8 10 15 18 17 1000 30 0 21 9 14 00 11 50 CZB03611 AV36 5 8 10 15 18 17 1200 36 0 26 5 14 00 11 50 CZB04211 AV SV48...

Page 7: ...36H17 1000 30 0 21 9 13 00 11 00 21 G FD036H21 1000 30 0 21 9 13 00 11 00 21 G FD042H21 1000 30 0 21 9 13 00 11 00 17 G FD046H17 1000 30 0 21 9 13 00 11 00 17 HC36 950 30 0 21 9 13 00 11 00 HD36 1000...

Page 8: ...MC PC30B 17 1000 30 0 21 9 13 50 11 00 P C V 9 B12 FC MC PC30B 17 1000 30 0 21 9 13 50 11 00 PV8 A12 FC MC PC36A 14 1000 30 0 22 3 14 00 11 50 PV9 A12 FC MC PC36A 14 1000 30 0 22 3 14 00 11 50 PV8 B16...

Page 9: ...48 0 36 1 13 05 11 00 PV9 D20 HD60 24 1600 48 0 36 1 13 25 11 00 PV9 C20 MC60D 21 1600 48 0 36 1 13 05 11 00 CZB06011 PV9 D20 FC MC PC60D 24 1620 55 0 39 3 13 25 11 00 PV8 C20 FC PC60C 21 1730 55 5 39...

Page 10: ...rmo stat 1H 1C auto manual change over electronic programmable deluxe 7 day thermostat 1H 1C auto manual change over electronic programmable For the most current accessory information refer to the pri...

Page 11: ...6 1 6 1 6 1 6 1 6 1 6 1 6 1 6 1 6 1 6 1 5 105 T C 12 7 14 6 13 8 15 6 16 8 14 3 15 9 15 0 16 9 17 9 15 8 17 3 16 2 18 1 19 0 S C 12 7 11 8 9 5 9 5 7 1 14 2 13 9 11 3 11 3 8 3 15 7 15 9 13 1 13 1 9 4 K...

Page 12: ...3 0 18 7 19 1 14 3 K W 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 0 2 1 2 0 2 0 105 T C 17 4 18 3 18 0 20 4 23 2 19 2 19 8 18 9 21 2 23 8 21 0 21 4 19 7 22 0 24 5 S C 17 2 15 7 13 2 13 4 10 9 18 9...

Page 13: ...21 0 20 4 16 3 27 2 27 1 23 0 22 5 18 1 K W 2 9 3 6 2 9 3 0 3 0 2 9 3 2 2 9 3 0 3 0 2 9 2 9 2 9 3 0 3 0 115 T C 21 6 21 9 22 9 23 6 26 7 23 4 23 5 23 6 25 3 27 9 25 1 24 7 24 4 27 0 29 2 S C 22 4 22 9...

Page 14: ...0 0 29 8 25 0 25 5 19 8 31 1 31 2 26 6 27 1 21 0 K W 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 115 T C 29 0 29 1 27 6 31 0 32 7 30 1 30 0 28 0 31 5 33 0 31 2 30 9 28 4 32 1 33 2 S C...

Page 15: ...6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 6 3 7 105 T C 33 5 34 7 34 5 37 5 42 0 35 0 35 7 35 3 38 4 42 8 36 5 36 7 36 2 39 3 43 6 S C 33 4 32 5 27 5 26 9 20 8 34 9 34 8 29 7 29 1 22 2 36 5...

Page 16: ...39 3 40 5 33 3 34 2 26 7 41 0 42 3 35 4 36 5 28 1 42 7 44 2 37 5 38 8 29 5 K W 4 2 4 2 4 1 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 3 4 2 105 T C 41 0 42 0 39 5 44 8 48 2 42 6 43 1 40 2 45 4 48 2 44...

Page 17: ...9 K W 5 0 5 0 4 9 5 1 5 2 5 0 5 0 5 0 5 1 5 2 5 0 5 0 5 0 5 1 5 2 105 T C 46 4 47 7 46 5 52 4 55 6 47 1 48 9 48 1 53 4 56 4 47 8 50 1 49 6 54 4 57 2 S C 36 9 44 6 40 7 37 2 27 8 39 0 47 1 41 7 39 5 29...

Page 18: ...246723 YTG J 1006 18 Unitary Products Group NOTES...

Page 19: ...246723 YTG J 1006 Unitary Products Group 19 NOTES...

Page 20: ...o change without notice Printed in U S A 246723 YTG J 1006 Copyright by York International JCI 2006 All rights reserved Supersedes 246723 YTG H 0906 Unitary 5005 Norman Products York OK Group Drive 73...