246723-YTG-J-1006
Unitary Products Group
13
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
CZB03011
INDOOR COIL MODEL NO.
G2FD030S17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
22.5
23.1
25.7
30.8
34.9
25.0
25.2
26.9
30.4
34.6
27.5
27.4
28.0
30.1
34.3
S.C.
23.0
19.2
18.2
21.2
17.3
25.7
23.9
20.8
22.5
18.1
28.3
28.5
23.4
23.9
19.0
K.W.
2.3
5.2
2.3
2.4
2.4
2.3
3.7
2.3
2.4
2.4
2.3
2.3
2.3
2.4
2.4
75
T.C.
25.8
28.5
29.0
31.5
35.5
28.0
29.8
29.9
32.5
36.7
30.3
31.1
30.8
33.6
37.9
S.C.
26.7
24.6
21.1
20.6
17.0
29.0
26.9
23.2
22.7
18.5
31.3
29.2
25.3
24.9
20.0
K.W.
2.0
2.0
2.0
2.0
2.1
2.0
2.0
2.0
2.0
2.1
2.0
2.0
2.0
2.0
2.1
85
T.C.
24.2
31.7
27.4
31.2
35.2
26.5
30.5
28.4
31.5
35.6
28.9
29.3
29.4
31.8
36.1
S.C.
24.9
21.9
19.7
20.9
17.2
27.3
25.4
22.0
22.6
18.3
29.8
28.9
24.3
24.4
19.5
K.W.
2.2
3.6
2.1
2.2
2.3
2.1
2.9
2.1
2.2
2.3
2.1
2.1
2.1
2.2
2.3
95
T.C.
23.3
21.5
25.9
28.6
32.3
25.5
24.6
26.8
29.4
33.0
27.6
27.7
27.7
30.2
33.8
S.C.
24.0
22.2
19.3
19.5
15.9
26.3
25.1
21.5
21.5
17.3
28.5
28.0
23.7
23.5
18.8
K.W.
2.5
3.6
2.5
2.6
2.6
2.5
3.1
2.5
2.6
2.6
2.5
2.5
2.5
2.6
2.6
105
T.C.
22.4
11.2
24.3
26.1
29.5
24.4
23.7
25.2
27.3
30.4
26.3
26.2
26.0
28.5
31.4
S.C.
23.2
22.6
19.0
18.2
14.6
25.2
24.8
21.0
20.4
16.3
27.2
27.1
23.0
22.5
18.1
K.W.
2.9
3.6
2.9
3.0
3.0
2.9
3.2
2.9
3.0
3.0
2.9
2.9
2.9
3.0
3.0
115
T.C.
21.6
21.9
22.9
23.6
26.7
23.4
23.5
23.6
25.3
27.9
25.1
24.7
24.4
27.0
29.2
S.C.
22.4
22.9
18.7
16.9
13.3
24.2
24.5
20.5
19.3
15.3
26.0
26.2
22.3
21.6
17.4
K.W.
3.2
3.6
3.2
3.3
3.4
3.2
3.4
3.2
3.3
3.4
3.3
3.2
3.2
3.4
3.4
125
T.C.
20.8
22.2
21.4
21.1
23.9
22.3
23.2
22.1
23.2
25.4
23.9
23.2
22.7
25.4
26.9
S.C.
21.6
23.3
18.4
15.6
12.1
23.1
24.3
20.0
18.2
14.4
24.7
25.3
21.7
20.7
16.7
K.W.
3.5
3.6
3.6
3.7
3.7
3.6
3.6
3.6
3.7
3.7
3.6
3.6
3.6
3.7
3.8
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MA12B
FC/MC30B
1.01
1.00
1.00
MA12B
FC/MC36B
1.02
1.01
1.00
MA12B
G*FD036H17
1.02
1.01
1.00
MA12B
G*FD036H21
1.02
1.01
1.00
MA12B
G*FD042H21
1.02
1.01
1.00
MA12B
G*FD046H17
1.02
1.01
1.00
MV12B
MC36B
1.04
1.03
0.95
AHP36
–
1.02
1.01
1.00
AHP30
–
1.02
1.01
1.00
AV36
–
1.02
1.01
0.95
F*FP030
–
1.00
1.00
1.00
F*FP036
–
1.04
1.03
1.00
–
FC/MC/PC/UC30
1.01
1.00
1.00
–
FC/MC/PC/UC36
1.02
1.01
1.00
–
G*FA036S14
1.01
1.00
1.00
–
G*FA036S17,21
1.00
1.00
1.00
–
G*FA048S17
1.02
1.01
1.00
–
G*FA048S21
1.02
1.01
1.00
–
G*FD035H14
1.00
1.00
1.00
–
G*FD036H17
1.02
1.01
1.00
–
G*FD036H21
1.02
1.01
1.00
–
G*FD042H21
1.02
1.01
1.00
–
G*FD046H17
1.02
1.01
1.00
–
HC36
1.02
1.01
1.00
–
HD36
1.02
1.01
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
PV8*A12
FC/MC/PC30A
1.02
1.01
1.00
PV9*A12
FC/MC/PC30A
1.02
1.01
1.00
PV8*B16
FC/MC/PC30B
1.02
1.01
1.00
PV9*B12
FC/MC/PC30B
1.02
1.01
1.00
PV8*A12
FC/MC/PC36A
1.04
1.03
0.95
PV9*A12
FC/MC/PC36A
1.04
1.03
0.95
PV8*B16
FC/MC/PC36B
1.04
1.03
0.95
PV9*B12
FC/MC/PC36B
1.04
1.03
0.95
PV8*C16
FC/MC/PC36C
1.04
1.03
0.95
PV9*C16
FC/MC/PC36C
1.04
1.03
0.95
PV8*B16
HC36
1.02
1.02
0.95
PV9*B12
HC36
1.02
1.02
0.95
PV8*C16
HD36
1.02
1.02
0.95
PV9*C16
HD36
1.02
1.02
0.95