12

Air purging

When relocate the unit to another place, perform evacuation using vacuum pump.

Make sure the refrigerant added into the air conditioner is liquid form in any case.
(Not applicable to the units with R22 refrigerant)

Open the valve stem until it hits against the stopper. Do not try to open it further.
Securely tighten the valve stem cap with a spanner or the like.
Valve stem cap tightening torque (See Tightening torque table in previous page ).

Outdoor
unit

Indoor
unit

Refrigerant

Flare nut

Stopper

Cap

Valve body

Packed valve

Half union

Gas side

Liquid side

A

C

D

B

Valve stem

Fig.22

Fig.23

When Using the Vacuum Pump

(For method of using a manifold valve, refer to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D,

valve charge

hose to a charge port of the low-pressure valve on the gas pipe side.

2. Connect the charge hose connection to the vacuum pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After

slightly loose the

flare nut of the Lo valve on the gas pipe side

check that the air is entering

(Operation noise

pump changes and a com

meter indicates

0 instead of minus)

5. After the evacuation is complete, fully close

manifold valve and stop the

operation of the vacuum pump.
Make evacuation for 15 minutes or more

compound meter indicates

-76cmHg (-1x10 Pa).

6. Turn the stem of the packed valve B about 45

counterclockwise for 6~7 seconds after the gas
coming out, then tighten the flare nut again. Make
sure the pressure display in the pressure indicator
is a little higher than the atmosphere pressure.

7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.

connect the manifold

starting evacuation,

and

of the vacuum

pound

the

handle Lo of the

and

check that the

o

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

Fig.24

Caution in handling the packed valve

5

Summary of Contents for 10 SEER 50HZ R22

Page 1: ...hen the power cord is damaged replacement work shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring standards by authorized person...

Page 2: ...f Improper installation will cause water leakage electrical shock or fire Please consult authorized dealer or specialist for the installation work Please note fault caused by improper installation is...

Page 3: ...f the outdoor unit are not attached securely it could result in a fire or electrical shock due to dust water etc Perform electrical work according to the installation manual and be sure to use an excl...

Page 4: ...ht or rain exposure make sure that heat radiation from the condenser is not restricted Ensure that the clearance around the back of the unit The front of the unit should have more than 200cm of cleara...

Page 5: ...left and right of the indoor unit is more than 12cm The indoor unit should be installed allowing a minimum clearance of 15cm from the ceiling Use a stud finder to locate studs to prevent unnecessary d...

Page 6: ...tructure and corresponding mounting points on the installation plate Dimensions are in mm unless otherwise stated 1 Determine hole positions according to the diagram detailed in Fig 5 Drill one 1 hole...

Page 7: ...rom side to side to see that it is securely hooked 3 Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping...

Page 8: ...se sloped downward to drain out the condensed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where t...

Page 9: ...C Roughness Burr Main cause for refrigerant leakage is due to defect in the flaring work Carry out correct flaring work using the following procedure 1 Use the piping kit accessory or pipes purchased...

Page 10: ...ing Flare nut Pipings Fig 18 ELECTRICAL WORK Electric safety regulations for the initial Installation 1 If there is serious safety problem about the power supply the technicians should refuse to insta...

Page 11: ...from a loop of the connective cable as illustrated in the installation diagram of indoor and outdoor units 4 Insulate unused cords conductors with PVC tape Process them so they do not touch any electr...

Page 12: ...oad 9 The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION C...

Page 13: ...Lo of the manifold valve 4 Operate the vacuum pump to evacuate After slightly loose the flare nut of the Lo valve on the gas pipe side check that the air is entering Operation noise pump changes and...

Page 14: ...safety check Gas leak check 1 Soap water method Do a leak test of all joints of the tubing both indoor and outdoor and both gas and liquid side service valves Bubbles indicate a leak 2 Leak detector...

Page 15: ...CS335 I 2200019440...

Reviews: