<5. List of Parameters>
5-2
IM 01C50T03-02EN
No.
Name
Description
RW
Remarks
Default
Upload/
download
parameter
D14 SENSOR1
DAMP
Sensor1 dumping
RW 0 to 100 sec
2 sec
D20
*2
S1 R0
Setting of sensor matching
reference resistance
RW The unit is ohms.
100.00 ohms
D21
*2
S1 A IEC
Primary coefficient setting of
sensor matching IEC standard
RW The unit is fixed to E-3. +3.90830 E-3
D22
*2
S1 B IEC
Secondary coefficient setting of
sensor matching IEC standard
RW The unit is fixed to E-7.
-5.77500 E-7
D23
*2
S1 C IEC
Tertiary coefficient setting of
sensor matching IEC standard
RW The unit is fixed to
E-12.
-4.18300 E-12
D24
*2
S1 ALPHA
Primary coefficient setting of
sensor matching CVD
RW The unit is fixed to E-3. +3.85055 E-3
D25
*2
S1 DELTA
Secondary coefficient setting of
sensor matching CVD
RW The unit is fixed to E0.
1.49979 E0
D26
*2
S1 BETA
Tertiary coefficient setting of
sensor matching CVD
RW The unit is fixed to E-1.
1.08634 E-1
D30
*1
SENSOR2
TYPE
Sensor2 input type
RW Same as D10
No
Connection
D31
*1
SENSOR2
WIRE
Sensor2 input wiring
RW 2 WIRE
3 WIRE
2 WIRE
D32
*1
SENSOR2
Sensor2 output value
R
―
D33
*1
SENSOR2
UNIT
Sensor2 unit selection
RW Same as D13
degC
D34
*1
SENSOR2
DAMP
Sensor2 dumping
RW 0 to 100 sec
2 sec
D40
*1*2
S2 R0
Setting of sensor matching
reference resistance
RW The unit is ohms.
+100.00 ohms
D41
*1*2
S2 A IEC
Primary coefficient setting of
sensor matching IEC standard
RW The unit is fixed to E-3. +3.90830 E-3
D42
*1*2
S2 B IEC
Secondary coefficient setting of
sensor matching IEC standard
RW The unit is fixed to E-7.
-5.77500 E-7
D43
*1*2
S2 CIEC
Tertiary coefficient setting of
sensor matching IEC standard
RW The unit is fixed to
E-12.
-4.18300 E-12
D44
*1*2
S2 ALPHA
Primary coefficient setting of
sensor matching CVD
RW The unit is fixed to E-3. +3.85055 E-3
D45
*1*2
S2 DELTA
Secondary coefficient setting of
sensor matching CVD
RW The unit is fixed to E0.
1.49979 E0
D46
*1*2
S2 BETA
Tertiary coefficient setting of
sensor matching CVD
RW The unit is fixed to E-1.
1.08634 E-1
D60 SELF CHECK Self-diagnosis
R
Same as A60
―
E
SET OUTPUT
Output setting
E10
LRV
Setting of range lower limit
RW -300 to +5000°C for
PV unit
-5000 to 5000°C if a
differential value such
as Sensor1 - Terminal
is mapped as PV
0.0
E11
URV
Setting of range upper limit
RW -300 to +5000°C for
PV unit
-5000 to 5000°C if a
differential value such
as Sensor1 - Terminal
is mapped as PV
100.0
E12
AUTO LRV
Automatic setting of range lower
limit
RW NO EXEC
EXEC
NO EXEC
E13
AUTO URV
Automatic setting of range upper
limit
RW NO EXEC
EXEC
NO EXEC
E20
AO DAMP
Current output dumping
RW 0 to 100 sec
0 sec