<3. Parameter Setting>
3-19
IM 01C50T03-02EN
NOTE
If you have selected the internal CJC, the settings
in Steps (2) and (3) are not required.
(2) Unit setting of cold junction compensation
temperature
Set the unit of cold junction compensation
temperature using the following parameters.
Parameter
Setting
value
Remarks
G11:CNST
CJC UNT
degC
Set the cold junction
compensation temperature in
degrees of centigrade (°C).
K
Set the cold junction
compensation temperature in
Kelvin (K).
degF
Set the cold junction
compensation temperature in
degrees of Fahrenheit (°F).
degR
Set the cold junction
compensation temperature in
degrees of Rankine (°R).
(3) Setting of cold junction compensation
temperature
Set the cold junction compensation temperature
using the following parameters.
Parameter
Setting
range
Remarks
G12:CNST
CJC TMP
-40 to 85
degC
When units other than
degC are set in (2),
the setting range is the
value converted from the
temperature shown on the
left to the setting unit.