<3. Parameter Setting>
3-5
IM 01C50T03-02EN
3.2.2 Sensor settings
When changing sensor type, it is necessary to
change the parameters related to each sensor.
Figure 3.1 shows both the wire connection to
input terminals of the transmitter, and sensor
type selection for parameters in each connection
case. Note that thermocouples and voltage value
input are categorized as Group A, and resistance
temperature detectors and resistance are
categorized as Group B. Check the connection
between input terminals and temperature sensors,
and set the correct sensor type and the number
of wire connections in “Sensor1” or “Sensor2” (for
2-input model).
The following shows the standard setup.
(1) Setting the sensor type
Set a sensor type using the following parameters.
Setting item
“Sensor1”
parameter
“Sensor2”
parameter
Sensor type
D10:SENSOR1
TYPE
D30:SENSOR2
TYPE
A sensor type can be selected from the following table.
Table 3.1
Selection of a sensor type
Setting value
Type
Group
Remarks
Type B IEC60584 Thermocouple A
Type E IEC60584 Thermocouple A
Type J IEC60584 Thermocouple A
Type K IEC60584 Thermocouple A
Type N
IEC60584
Thermocouple A
Type R
IEC60584
Thermocouple A
Type S IEC60584 Thermocouple A
Type T IEC60584 Thermocouple A
Type C
IEC60584
Thermocouple A
Type W3
ASTM988
Thermocouple A
Type L DIN43710 Thermocouple A
Type U
DIN43710
Thermocouple A
Pt100 IEC60751 Resistance
temperature
detector
B
Pt200 IEC60751 Resistance
temperature
detector
B
Pt500 IEC60751 Resistance
temperature
detector
B
Pt1000
IEC60751
Resistance
temperature
detector
B
JPt100 JIS
Resistance
temperature
detector
B
Setting value
Type
Group
Remarks
Ni120 STI INC
Resistance
temperature
detector
B
Cu10 SAMA
RC21-4
Resistance
temperature
detector
B
Sensor Matching Resistance
temperature
detector
B
Only
selectable
when
additional
spec code/
CM1 is given
ohm
Resistance
B
mV
DC voltage
A
No connection
No
connection
-
NOTE
If a sensor of Group A is used, the number of
wire connections is automatically changed to
“2 WIRE”. In such a case, it is not necessary
to “set the number of wire connections” of Item
(2) below. If “No connection” is set, a number of
wire connections can be set, however, it is made
invalid.
(2) Setting the number of wire connections
Set a number of wire connections using the
following parameters. However, this setup is only
required when the Group of the sensor type is “B”.
This setup is not required for a sensor of Group A.
Setting item
“Sensor1”
parameter
“Sensor2”
parameter
Number of wire
connections
D11:SENSOR1
WIRE
D31:SENSOR2
WIRE
Select a number of wire connections from the
following options.
Sensor
Option
Remarks
Sensor1
2 WIRE, 3 WIRE,
4 WIRE
If “4 WIRE” is
selected, “Sensor2”
cannot be used.
Sensor2
2 WIRE, 3 WIRE
NOTE
If “4 WIRE” is selected as the number of wire
connections of Sensor1, Sensor2 cannot be used
even for a 2-input model temperature transmitter.
Therefore, the sensor type at Sensor2 side is
changed to “No connection” automatically.