<5. Parameters Lists>
5-2
IM 01C50T01-02EN
Item
Parameter
Description
Write
Initial
Setting
Sensor2
Configuration
Sensor2
Type and
wire
set Sns2 Probe
Specify sensor type and number of wires.
M
Sensor2
type
Sns2 Probe Type
Sensor2 type
R
Pt100
Sensor2 wire
Sns2 Wire
Number of Sensor2 wires
R
3 Wire
Sensor2 unit
Sns2 Unit
°C, K,°F, °R, mV or ohm
RW
°C
Sensor2
damping
Sns2 Damp
Specify the response time of sensor1 input
within 0 to 100 seconds.
RW
2s
Sensor2
matching
set Sns2 Matching
This function is available only when optional
specification /CM1 is specified. Select “Enable”
or “Disable”.
M
Sns2 CVD
(R0, A, B, C, AI pha,
Delta, Beta)
Sensor2 matching co-efficient.
R
Sensor
backup
recover Sensor
Recover Backup Operation.
M
Sensor Backup
State
Show the backup state.
R
Terminal
Temperature
Terminal
temp. unit
Term Unit
Specify from °C, K,°F, or °R
RW
°C
Terminal
damping
Term Damp
Specify the response time of terminal
temperature within 0 to 100 seconds.
RW
2 s
CJC function Set CJC Type
M
CJC Type
“Internal CJC” to use temperature or “Constant
CJC” to use constant value.
R
Internal
CJC
Fixed CJC Temp
Specify constant value using CJC function.
R
Fixed CJC Unit
R
Output
Sensor burn-
out output
AO Sensor BO Dir
Select Sensor Burnout direction.
RW
High
AO Sensor BO Unit
Select mA or %
RW
AO Sensor BO Usr
Val
Specify value within 3.6 to 21.6 (mA) or -2.5 to
110%
RW
Output in
CPU failure
AO Alarm Typ
Show the current setting of the output direction
in hardware failure which is set using switch on
a MAIN assembly
R
Burst mode Burst mode
Off or ON
M
Off
set Easy Burst
Configure Burst mode
M
set Detailed Burst
Configure Burst mode
M
Burst Command
Cmd 1:PV
Cmd 2:% range/current
Cmd 3:Dyn vars/current
Cmd 9:Device vars w/status
Cmd33:Device vars
Cmd 48:Read Additional Device Status
M
Burst Variable Code Device Variable for the Burst Message Max 4
slots.
M
Update Period
Update Period for Burst mode
M
Max Update Period Max Update Period for Burst mode
M
Burst Msg Trigger
Mode
Burst Trigger Mode Selection Code
Continuous, Window, Rising, Falling,
On-change
M
Burst Trigger Class
RW
Burst Trigger Units
Unit for Burst Trigger
RW
Burst Trigger Level
M
Multi-drop
mode
Poll addr
0 to 63
RW
0
Loop Current mode Enabled: 4 to 20 mA output
Disabled: 4 mA fixed
RW
Disabled