<5. Parameters Lists>
5-1
IM 01C50T01-02EN
5. Parameters Lists
RW: read/write
R: read only, M: Method
Item
Parameter
Description
Write
Initial
Setting
Memory
Tag
Up to 8 characters
RW
Long Tag
Up to 32 characters
RW
Descriptor
Up to 16 characters
RW
Message
Up to 32 characters
RW
Date
RW
Process
variable
Engineering
Unit
PV Unit (SV,TV, QV) Process variable unit
RW
°C
Range
LRV/URV
Specify the calibration range.
RW
LRV: 0
URV: 100
Apply values
Value for 4 and 20 mA signal is set with actual
input applied
M
─
Damping
time
constant
AO Damping
Specify the response time of process variable
within 0 to 100 seconds.
RW
8 s
Damping
holding point
AO Damp Point
Specify the % of the output range. When the
amount of variation is larger than the set value,
it does not perform the dumping process.
RW
0%
Variable
mapping
PV is (SV, TV, QV)
Sensor1, Terminal, Sensor1-Terminal (for
single input)
Sensor2, Sensor1-Sensor2, Sensor2-Sensor1,
Average, Sensor2-Terminal: (for dual input)
Sensor backup
RW
PV:
Sensor1
SV:
Terminal
TV:
Terminal
QV:
Terminal
Sensor1
Configuration
Sensor1
Type and
wire
set Sns1 Probe
Specify sensor type and number of wires.
M
Sensor1
type
Sns1 Probe Type
Sensor1 type.
R
Pt100
Sensor1 wire
Sns1 Wire
Number of Sensor1 wires
R
3 Wire
Sensor1 unit
Sns1 Unit
°C, K,°F, °R, mV or ohm
RW
°C
Sensor1
damping
Sns1 Damp
Specify the response time of sensor1 within 0
to 100 seconds.
RW
2s
Sensor1
matching
set Sns1 Matching
This function is available only when optional
specification /CM1 is specified. Select enable
or disable.
M
Sns1 CVD
(R0, A, B, C, AI pha,
Delta, Beta)
Sensor1 matching co-efficient.
R