![YOKOGAWA YTA610 User Manual Download Page 40](http://html1.mh-extra.com/html/yokogawa/yta610/yta610_user-manual_3854331040.webp)
<4. Diagnostics >
4-8
IM 01C50T01-02EN
PV
Out
of
Limit
Non-PV
Out
of
Limit
AO
Saturated
AO
Fixed
More
Status
A
vailable
Device
Malfunction
Device
V
ariable
Alert
NV
memory
failure
RAM error
Env
Cnd
out
of
range
Electronic
failure
bit
0
1
2
3
4
7
1
1
2
5
6
Name
bit
Description
Field Device Status
Extended
Device
Status
Standardized
Status0
Device Specific Status 5
1
LRV Too Low
x
2
LRV Too High
x
3
URV Too Low
x
4
URV Too High
x
5
Span Too Small
x
Device Specific Status 14
0
Illegal PV Cfg
x
1
Illegal Sensor1 Cfg
x
2
Illegal Sensor2 Cfg
x
Device Specific Status 15
0
Output Manual Mode
x
*1:
Applicable only for YTA710.
Table 4.6
NE-107 Condensed Status and Status Mask
Name
bit
Description
NAMUR-107 Mask Available
Initial Setting
Field Device Status
0
PV Out of Limits
S
No mask
1
Non-PV Out of Limits
S
No mask
2
AO Saturated
S
No mask
3
AO Fixed
No mask
4
More Status Available
No mask
5
Cold Start
No mask
6
Config Changed
No mask
7
Device Malfunction
No mask
Extended Device Status
0
Maintenance Required
No mask
1
Device Variable Alert
S
No mask
3
Failure
No mask
4
Out of Specification
No mask
5
Function Check
No mask
Standardized Status0
0
Simulation Active
C
No mask
1
NV memory failure
F
No mask
2 RAM error
F
No mask
3
Watchdog Reset
F
No mask
5
Env Cnd Out of Range
No mask
6
Electronic failure
F
No mask
7
Device Config Locked
No mask
Standardized
StatuSensor1
0
Status Sim Active
No mask
2
Event Overflow
No mask
Device Specific Status 0
0
CPU Fail
F
No mask
1
Sensor NV Fail
F
No mask
2
Temp NV Fail
F
No mask
3
AD Converter Fail
F
No mask
4
Main Rvrs Calc Fail
F
No mask
5
Temp Rvrs Calc Fail
F
No mask
6
Temp Voltage Fail
F
No mask
7
Comm NV Fail
F
No mask