![YOKOGAWA YTA610 User Manual Download Page 23](http://html1.mh-extra.com/html/yokogawa/yta610/yta610_user-manual_3854331023.webp)
<3. Parameter Setting >
3-16
IM 01C50T01-02EN
(2) Display Selection
• Procedure to call up the display
Device setup → Detailed setup → Display
Setup
→ Disp1 Variable: Select from Table3.1.
→ Disp2 Variable: Select from Table3.1.
→ % Display On/Off: Select On/Off.
→ mA Display On/Off: Select On/Off.
→ Bar Graph On/Off: Select On/Off.
(3) Display Resolution
• Procedure to call up the display
Device setup → Detailed setup → Display
Setup
→ Disp1 Decimal Point
→ Disp2 Decimal Point
→ % Decimal Point
→ mA Decimal Point
Select the decimal point from 0, 1, 2 or 3.
(4) Setting Display Cycle
• Procedure to call up the display
Device setup → Detailed setup → Display
Setup → Display Cycle
High: 1.2 seconds
Mid (Default): 2.4 seconds
Low: 3.6 seconds
(5) Display Information
Following information is displayed on lower level of
the display.
• Procedure to call up the display
Device setup → Detailed setup → Display
Setup → Disp Info Select
Process variable name: Parameter
Process variable unit: Unit
Status of process variable: Status
Sensor type: Sensor Type
Number of wiring: Sensor Wire
3.5.5 Write Protect
(1) Software write protect
The transmitter configured data is saved by using a
write protection function. The write protection status
is set to “Yes” when 8 alphanumeric characters are
entered in the New password field and transferred
to the transmitter. When write protection is set to
”Yes,” the transmitter does not accept parameter
changes. When the same eight alphanumeric string
entered in the New password field is also entered
in the Enable wrt 10 min field and transferred to the
transmitter, it will be possible to change transmitter
parameters during a 10 minute period. To change
the transmitter from the write protection ”Yes” status
back to write protection ”No” status, use Enable wrt
10min to first release the write protection function
and then enter eight spaces in the New password
field.
• Procedure to call up the display
Device setup → Detailed setup → Device
information → Write Protect
→ Write protect: Display current write protect
mode (Yes: protected, No: not protected)
→ release WP Mode: Release the write protect
function for 10 min.
→ set New Password: Set the new password or
change the password.
(2) Software seal
When the joker password has been used to
release write protection, this parameter displays
“Break,” and when protection is cancelled using the
password set using “set New Password”, it returns
to “Keep.”
NOTE
If you should forget your password, the joker
password can be used to temporarily release
write protection function. To obtain the joker
password, please contact your nearest
YOKOGAWA sales office.
(3) Hardware write protect
See IM 01C50G01-01EN, section 3.2 “Hardware
Error Burnoat and Hardware Write Protect Switch.”