Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
90
Parameter Display
Default Setting User Setting
Fail-safe relay 3
Fls 3
Off
Fail-safe relay 4
Fls 4
Off
Display 1 analog out
Dis 1
4.000
Output 1 value
Out 1
4.000 mA
Display 2 analog out
Dis 2
20.000
Output 2 value
Out 2
20.000 mA
Source analog output
Source
Rate/process
Overrange output
O-rang
21.000 mA
Underrange output
u-rang
3.000 mA
Loop break output
break
1.000 mA
Maximum output
mAx
23.000 mA
Minimum output
min
1.000 mA
F1 function key
F1
Reset max & min
Password 1
Pass 1
000000 (unlocked)
Password 2
Pass 2
000000 (unlocked)
Password 3
Pass 3
000000 (unlocked)
Total password
Total
000000 (unlocked)
Grand total password
Gtotal
000000 (unlocked)
Other Parameters