
Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
18
Configuration for 12 or 24 VDC Power Option
Warning!
Do not exceed voltage rating of the selected
configuration.
Meters equipped with the 12/24 VDC power option are shipped from
the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power connector, for 12
V as shown below.
MAIN BOARD
24 VDC
12 VDC
POWER
J9
12 V
24 V
J9 CONFIGURATION
Factory
Default
M-LINK
+
_
Figure 4: Jumper Configuration for 12/24 VDC Power