Model YPP6200 Analog Input Rate/Totalizer
Instruction Manual
76
Multi-Point Linearization (
Linear
)
Meters are set up at the factory for linear function with 2-point
linearization. Up to 32 linearization points can be selected under the
linear function.
The multi-point linearization can be used to linearize the
display for non-linear signals such as those from level transmitters used
to measure volume in odd-shaped tanks or to convert level to flow using
weirs and flumes with complex exponent.
Square Root Linearization (
Square
)
The square root function can be used to linearize the signal from a
differential pressure transmitter and display flow rate in engineering
units.
Programmable Exponent Linearization (
Prog E
)
The programmable exponent can be used to linearize the signal from
level transmitters in open-channel flow applications using weirs and
flumes.
Round Horizontal Tank Linearization (
rHt
)
This function automatically calculates the volume in a round horizontal
tank with flat ends. This function is only used when
Total
is set to
no
.
Set the display for the desired decimal point and engineering units
before entering the round horizontal tank function. Select units, inches or
cm for the tank dimension. Enter the diameter and the length in inches
and the results are given in US gallons.
The meter can be scaled to display the volume in any engineering unit.
Note: After Scale is displayed continue pressing the Enter button until
the meter completes the scaling of the input and display values.