Setting
1
2
3
App
1
2
3
5
6
7
8
4
No.
Parameter
Name
Symbol
Description
Setting Range Factory-set
Value
Display
Conditions
E
Setting
Parameters
(alarm)
SET(ALM)
E05
Alarm 1 Set
Point
SET POINT1 Alarm 1 set point
Setting range SKYD-302: -999.9 to 999.9%
(*1) SKYD-304: -19999 to 32000 (decimal point position set at DP1)
Default SKYD-302: 100.0%
SKYD-304: When ALM1 ACTION= DIRECT, SCH1-SCL1
When ALM1 ACTION= REVERSE, SCL1-SCH1
On the SKYD-304, this range is initialized when SCH1 and/or SCL1
are changed.
Display on all
E06
Alarm 2 Set
Point
SET POINT2 Alarm 2 set point
Setting range SKYD-302: -999.9 to 999.9%
(*1) SKYD-304: -19999 to 32000 (decimal point position set at DP1)
Default SKYD-302: -100.0%
SKYD-304: When ALM2 ACTION=DIRECT, SCH1-SCL1
When ALM2 ACTION=REVERSE, SCL1-SCH1
On the SKYD-304, this range is initialized when SCH1 and/or SCL1
are changed.
E07
Alarm 1 Action ALM1 ACTION Displays the direction (direct/reverse)
of action of alarm 1.
The setting can be changed on
models except SKYD-304.
On the SKYD-304, displays the state
of the jumpers on the main board.
DIRECT
REVERSE
DIRECT
Displayed on
all
E08
Alarm 2 Action ALM2 ACTION Displays the direction (direct/reverse)
of action of alarm 2.
The setting can be changed on
models except SKYD-304.
On the SKYD-304, displays the state
of the jumpers on the main board.
DIRECT
REVERSE
REVERSE
E09
Alarm 1
Hysteresis
HYSTERESIS1 Sets the hysteresis until the alarm 1 alarm state is canceled.
Setting range SKYD-302: 0.0 to 100.0%
SKYD-304: 0 to 100% of span (EUS) after scaling
Default SKYD-302: 2.0%
SKYD-304: 2.0% of span (EUS) after scaling
On the SKYD-304, this range is initialized when SCH1 and/or SCL1
are changed.
E10
Alarm 2
Hysteresis
HYSTERESIS2 Sets the hysteresis until the alarm 2 alarm state is canceled.
The setting range and default are the same as alarm 1 hysteresis.
On the SKYD-304, this range is initialized when SCH1 and/or SCL1
are changed.
E15
Alarm 1 ON
Delay
ON DELAY1
Sets the dead time until the alarm is
output after alarm 1 enters the alarm
state.
0 to 999 s
0 s
E16
Alarm 2 ON
Delay
ON DELAY2
Sets the dead time until the alarm is
output after alarm 2 enters the alarm
state.
0 to 999 s
0 s
E17
Alarm 1 OFF
Delay
OFF DELAY1 Sets the dead time until alarm output
is stopped after alarm 1 is released
from the alarm state.
0 to 999 s
0 s
E18
Alarm 2 OFF
Delay
OFF DELAY2 Sets the dead time until alarm output
is stopped after alarm 2 is released
from the alarm state.
0 to 999 s
0 s
E19
Alarm 1 Relay
Action
RLY1 ACTION Specifies the direction of alarm 1 relay
action.
NRM DE-ENERGIZED: De-energized
during normal operation
NRM ENERGIZED: Energized during
normal operation
NRM
DE-
ENERGIZED
NRM
ENERGIZED
NRM
DE-
ENERGIZED
Displayed on
all
E20
Alarm 2 Relay
Action
RLY2 ACTION Specifies the direction of alarm 2 relay
action.
NRM DE-ENERGIZED: De-energized
during normal operation
NRM ENERGIZED: Energized during
normal operation
NRM
DE-
ENERGIZED
NRM
ENERGIZED
NRM
DE-
ENERGIZED
E60
Self Check
SELF CHK
Displays the result (GOOD/ERROR) of the self check.
*1: For details on the Alarm Setting and Accuracy Warranty Range, see "2.1 Standard Specifications."
5.4 Parameter List