5-7
IM 01B04K01-02E
Setting
1
2
3
App
1
2
3
5
6
7
8
4
Setting Parameters
Display the desired parameter (e.g. alarm set point), and follow the procedure below to
change its set point.
F0505.ai
1
ALM
SP
2
SET
1
2
1
ALM
SP
2
SET
1
2
1
AL M
SP
2
1
2
(1) Input value (60.00) is displayed at power ON.
Press the - key. The SP1 lamp lights, and the alarm 1 set point is displayed.
(2) The alarm 1 set point (80.00) is displayed.
Press the - key.
In the case of the SKYD-104, the SP1 lamp goes out, and the
input value is displayed.
In the case of the SKYD-204/304, the SP2 lamp lights, and
the alarm 2 set point is displayed.
Alarm 2 set point (30.00) is
displayed. (SKYD-204/304 only)
(4) Set the alarm set point. (Change the alarm 1 set point to "70.00" from "80.00".)
Alarm set points whose SP lamp is lit can be changed.
Press the - key.
The uppermost digit on the display flashes.
Hold down the key to move the flashing section to the digit
on the right.
Press the -
key.
This increments the value at the flashing digit. Hold down the
key to feed the value to "7".
Press the -
key.
All parameter digits flash. Pressing the key again
causes "70.00" to light. (This fixes the new parameter
settings.).
SET
SET
(3) Press the ENBL switch to enter setting change enable state.
Figure
5-5
Setting
Parameters
● When the Parameter Write Protect jumper on the main board is set to “ON”, the
SKYD will not advance to the setting change mode. In this state, “LOC” is dis-
played on the display setter.
● Do not turn off the power of the instrument during parameter setting.
5.3 Setting of Parameters