5-16
IM 01B04K01-02E
No.
Parameter Name
Symbol
Description
Setting
Range
Factory-set
Value
Display
Conditions
E
Setting
Parameters(alarm)
SET(ALM)
E01
Alarm 1 Set Point
SET POINT1 Alarm 1 set point
Setting range SKYD-200: -999.9 to 999.9%
(*1) SKYD-204: -19999 to 32000 (decimal point position set at
DP1)
Default SKYD-200: 100.0%
SKYD-204: When ALM1 ACTION=DIRECT, SCH1
When ALM1 ACTION=REVERSE, SCL1
On the SKYD-204, this range is initialized when SCH1 and/or
SCL1 are changed.
Displayed on
SKYD-200, -204
E02
Alarm 2 Set Point
SET POINT2 Alarm 2 set point
Setting range SKYD-200: -999.9 to 999.9%
SKYD-204: -19999 to 32000 (decimal point position set at
DP1)
Default SKYD-200: 100.0%
SKYD-204: When ALM2 ACTION=DIRECT, SCH1
When ALM2 ACTION=REVERSE, SCL1
On the SKYD-204, this range is initialized when SCH1 and/or
SCL1 are changed.
Displayed on
SKYD-200, -204
E03
Alarm 1 Set Point
SET POINT1 Alarm 1 set point
Setting range SKYD-201: 0.0 to 100.0 (default: 10.0)
Displayed on
SKYD-201
E04
Alarm 2 Set Point
SET POINT2 Alarm 2 set point
Setting range SKYD-201: 0.0 to 100.0 (default: 10.0)
Displayed on
SKYD-201
E07
Alarm 1 Action
ALM1 ACTION Displays the direction (direct/
reverse) of action of
alarm 1.
The setting can be changed on
models except SKYD-204.
On the SKYD-204, displays the
state of the jumpers on the main
board.
DIRECT
REVERSE
DIRECT
Displayed on all
E08
Alarm 2 Action
ALM2 ACTION Displays the direction (direct/
reverse) of action of
alarm 2.
The setting can be changed on
models except SKYD-204.
On the SKYD-204, displays the
state of the jumpers on the main
board.
DIRECT
REVERSE
REVERSE
E09
Alarm 1 Hysteresis HYSTERESIS1 Sets the hysteresis until the alarm 1 alarm state is canceled.
Setting range Except SKYD-204: 0.0 to 100.0%
SKYD-204: 0 to 100% of span (EUS) after scaling
Default Except SKYD-204: 2.0%
SKYD-204: 2.0% of span (EUS) after scaling
On the SKYD-204, this range is initialized when SCH1 and/or
SCL1 are changed.
E10
Alarm 2 Hysteresis HYSTERESIS2 Sets the hysteresis until the alarm 2 alarm state is canceled.
The setting range and default are the same as alarm 1
hysteresis.
On the SKYD-204, this range is initialized when SCH1 and/or
SCL2 are changed.
E15
Alarm 1 ON Delay
ON DELAY1
Sets the dead time until the
alarm is output after alarm 1
enters the alarm state.
0 to 999 s
0 s
E16
Alarm 2 ON Delay
ON DELAY2
Sets the dead time until the
alarm is output after alarm 2
enters the alarm state.
0 to 999 s
0 s
E17
Alarm 1 OFF Delay OFF DELAY1 Sets the dead time until alarm
output is stopped after alarm 1
is released from the alarm state.
0 to 999 s
0 s
E18
Alarm 2 OFF Delay OFF DELAY2 Sets the dead time until alarm
output is stopped after alarm 2
is released from the alarm state.
0 to 999 s
0 s