5-19
IM 01B04K01-02E
Setting
1
2
3
App
1
2
3
5
6
7
8
4
5.4.3
SKYD-30x Parameter List
No.
Parameter
Name
Symbol
Description
Display
Conditions
Initial
display
01
Model Name
MODEL
Displays the model name.
Displayed
on all
02
Tag Number
TAG NO
Displays the tag number that is set.
03
Self Check
SELF CHK
Displays the result (GOOD/ERROR) of the self check.
A
Display 1
DISPLAY1
A01
Analog Input 1 INPUT1
Input value before input processing (square root or scaling)
(unit: V)
Displayed on
SKYD-304
A02
Analog Input 2 INPUT2
Input value before input processing (square root or scaling)
(unit: V)
A08
Input Deviation INPUT DEV
Deviation value (PV1-PV2) after input processing
Displayed
on all
A15
Alarm 1 Relay
Display
RLY1 STATUS
Displays the state of the alarm 1 relay.
DE-ENERGIZED: De-energized
ENERGIZED: Energized
A16
Alarm 2 Relay
Display
RLY2 STATUS
Displays the state of the alarm 2 relay.
DE-ENERGIZED: De-energized
ENERGIZED: Energized
A54
Status Display
STATUS
Displays the value added to the value (Hex) indicating the
self check result.
0000: Normal
0001: EEPROM error
0002: EEPROMSUM error
0004: Low input cut state
0008: Input range exceeded
0010: Setting error
0040: Power interruption during operation
1000: A/D conversion error
A55
Parameter Write
Protect
WRT PROTECT Displays the state of the Parameter Write Protect jumper.
OFF: Setting of parameters enabled
ON: Setting of parameters disabled
A56
REV NO.
REV NO.
Displays the device revision No.
A58
MENU REV
MENU REV
Displays the revision No. of the parameter group.
A60
Self Check
SELF CHK
Displays the result (GOOD/ERROR) of the self check.
B
Display 2
DISPLAY2
B01
Analog Input 1 Same as item A
B02
Analog Input 2
B08
Input Deviation
B15
Alarm 1 Relay
Display
B16
Alarm 2 Relay
Display
B60
Self Check
5.4 Parameter List