5-15
IM 01B04K01-02E
Setting
1
2
3
App
1
2
3
5
6
7
8
4
No.
Parameter Name
Symbol
Description
Setting Range
Factory-set
Value
Display
Conditions
D
Setting Parameters SET(I/O)
D01
Tag Number 1
TAG NO.1
8 alphanumerics can be
entered.
Displayed on all
D02
Tag Number 2
TAG NO.2
8 alphanumerics can be
entered.
D03
Comment 1
COMMENT1 8 alphanumerics can be
entered.
D04
Comment 2
COMMENT2 8 alphanumerics can be
entered.
D17
Linearization 1
LINEARIZE1 Specifies square root
calculation ON/OFF.
OFF
SQR
OFF
Displayed on
SKYD-200, -204
D19
Low Cut 1
LOW CUT1
Specifies low-cut point
during square root
calculation.
0.3 to 100.0 %
1.0 %
Displayed on
SKYD-200, -204
Displayed when
LINEARIZE1=SQR
D40
Input Decimal Point
Position
DP1
Sets the position of the
decimal point for the input
scale (SCH1, SCL1).
#####
####.#
###.##
##.###
####.#
Displayed on
SKYD-204
D41
Input Scale L
SCL1
Sets the conversion
standard value at 1V input
to scale and display the
input value in engineering
units.
-9999 to 9999
(engineering unit)
0.0
D42
Input Scale H
SCH1
Sets the conversion
standard value at 5V input
to scale and displays the
input value in engineering
units.
-9999 to 9999
(engineering unit)
100.0
D46
PV1
PV1
Displays the input value
after input processing
(scaling).
D47
Input 1 Bias
BIAS1
Adds the bias value to
the value after input
processing, and displays as
the PV1.
±10% of scaled
span (EUS) *1
±0% of span
(EUS) *1
D51
Display Mode
DSP MODE
Selects the display setter
state after 30 minutes
elapses after a key switch
operation.
OFF: Power save mode
Only the decimal point
is displayed.
ON: Constant ON mode
Data is displayed at
all times regardless of
elapsed time.
OFF
ON
ON
D60
Self Check
SELF CHK
Result of self check
(GOOD/ERROR) of the self check.
Displayed on all
*1: Initialized when changing SCH1, SCL1
5.4 Parameter List