background image

IM 05P02C41-15EN  page 2/14

n

 Mounting the Instrument Main Unit

Provide an instrumented panel steel sheet of 1 to 10 mm thickness.

After opening the mounting hole on the panel, follow the procedures below to install 

the controller:

1)  Insert the controller into the opening from the front of the panel so that the 

terminal board on the rear is at the far side.

2)  Set the brackets in place on the top and bottom of the controller as shown in the 

figure below, then tighten the screws of the brackets. Take care not to overtighten 

them.

 

Bracket

(top mounting hardware)

Terminal board

Bracket

(bottom mounting hardware)

Panel

Insert a screwdriver into the

brackets to tighten the screws.

Direction to insert the

controller

Appropriate

tightening torque:

0.25 N

m

Insert the controller

into the opening at

the front of the panel.

CAUTION

•  Tighten the screws with appropriate tightening torque within 0.25 

N•m. Otherwise it may cause the case deformation or the bracket 

damage.

•  Make sure that foreign materials do not enter the inside of the

  instrument through the case’s slit holes.

n

 External Dimensions and Panel Cutout Dimensions

(25)

(53) (2.09)

[(N-1)×96+92]

117 (4.61) min.

145 (5.71)

min.

+0.8

0

+0.8

0

92

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N≥5.

65 (2.56)

20  (0.79)

11

(0.43)

UP55A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket

94.6 (3.72)

91.6 (3.61)

105.2 (4.14)

Unit: mm (approx. inch)

96 (3.78)

96 (3.78)

• General mounting

• Side-by-side close mounting

Terminal cover

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.8

0

92

+0.03

0

(3.62        )

(0.98)

+0.03

0

(3.62        )

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×3.78+3.62]         )

+0.03

0

4.  Hardware Specifications

WARNING 

This instrument is for Measurement Category I (CAT.I). Do not use it 

for measurements in locations falling under Measurement Catego-

ries II, III, and IV.

Internal Wiring

Outlet

Entrance IV

Cable

III

T

I

II

Category Measurement 

category

Description

Remarks

I

CAT.I

For measurements performed on circuits not 

directly connected to MAINS.

-

II

CAT.II

For measurements performed on circuits di

-

rectly connected to the low-voltage installation.

Appliances, portable equip-

ments, etc.

III

CAT.III

For measurements performed in the building 

installation.

Distribution board, circuit 

breaker, etc.

IV

CAT.IV

For measurements performed at the source of 

the low-voltage installation.

Overhead wire, cable 

systems, etc.

n

 Input Specifications

●Universal Input (Equipped as standard)

•  Number of inputs: 1

•  Input type, instrument range, and measurement accuracy: See the table below.

Input Type

 Instrument Range

Accuracy

ºC

ºF

Thermo-

couple

K

-270.0 to 1370.0ºC -450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C 

 

±2% of instrument range ±1 digit for 

less than -200.0°C of thermocouple K 

±1% of instrument range ±1 digit for 

less than -200.0°C of thermocouple T

-270.0 to  1000.0ºC -450.0 to 2300.0ºF

-200.0 to  500.0ºC

-200.0 to 1000.0ºF

J

-200.0 to 1200.0ºC -300.0 to 2300.0ºF

T

-270.0 to 400.0ºC

-450.0 to 750.0ºF

0.0 to  400.0ºC

-200.0 to 750.0ºF

B

0.0 to 1800.0ºC

32 to 3300ºF

±0.15% of instrument range ±1 digit 

for 400°C or more

 

±5% of instrument range ±1 digit for 

less than 400°C

S

0.0 to 1700.0ºC

32 to 3100ºF

±0.15% of instrument range ±1 digit 

R

0.0 to 1700.0ºC

32 to 3100ºF

N

-200.0 to 1300.0ºC -300.0 to 2400.0ºF

±0.1% of instrument range ±1 digit

±0.25% of instrument range ±1 digit 

for less than 0°C

E

-270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C

 

±1.5% of instrument range ±1 digit for 

less than -200.0°C of thermocouple E.

L

-200.0 to 900.0ºC

-300.0 to 1600.0ºF

U

-200.0 to 400.0ºC

-300.0 to 750.0ºF

0.0 to 400.0ºC

-200.0 to 1000.0ºF

W

0.0 to 2300.0ºC

32 to 4200ºF

±0.2% of instrument range ±1 digit 

(Note 2)  

Platinel 2

0.0 to 1390.0ºC

32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit  

PR20-40

0.0 to 1900.0ºC

32 to 3400ºF

±0.5% of instrument range ±1 digit for 

800°C or more 

 

Accuracy is not guaranteed for less 

than 800°C.  

W97Re3-

W75Re25

0.0 to 2000.0ºC

32 to 3600ºF

±0.2% of instrument range ±1 digit  

RTD

JPt100

-200.0 to 500.0ºC

-300.0 to 1000.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-150.00 to  150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Pt100

-200.0 to 850.0ºC

-300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-200.0 to 500.0ºC

-300.0 to 1000.0ºF

-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Standard signal

0.400 to 2.000 V

±0.1% of instrument range ±1 digit

1.000 to 5.000 V

4.00 to 20.00 mA

DC voltage/current

0.000 to 2.000 V

0.00 to 10.00 V

0.00 to 20.00 mA

-10.00 to 20.00 mV

0.0 to 100.0 mV

The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power 

frequency at 50/60 Hz.

Note 

1:  ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range 

 

  between -100 and 200°C.

Note 2:  W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988

• Input sampling (control) period: Select from 100 and 200 ms

• Burnout detection:

    Functions at TC, RTD, and standard signal.

    Upscale, downscale, and off can be specified.

    For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4

 

  mA or less.

• Input bias current: 0.05 µA (for TC or RTD)

• Measured current (RTD): About 0.16 mA

• Input resistance:

    TC or mV input: 1 MΩ or more

    V input: About 1 MΩ

    mA input: About 250 Ω

• Allowable signal source resistance:

    TC or mV input: 250 Ω or less

   

Effects of signal source resistance: 0.1 µV/Ω or less

    DC voltage input: 2 kΩ or less

   

Effects of signal source resistance: About 0.01%/100 Ω

•  Allowable wiring resistance:

    RTD input: Max. 150 Ω/wire  (The conductor resistance between the three wires 

 

  shall be equal.)

    Wiring resistance effect: ±0.1ºC/10 Ω

•  Allowable input voltage/current:

    TC, mV, mA and RTD input: ±10 V DC

    V input: ±20 V DC

    mA input: ±40 mA

•  Noise rejection ratio:

    Normal mode: 40 dB or more (at 50/60 Hz)

    Common mode: 120 dB or more (at 50/60 Hz)

    For 100-240 V AC, the power frequency can be set manually.

    Automatic detection is also available.

    For 24 V AC/DC, the power frequency can be set manually.

•  Reference junction compensation error:

    ±1.0ºC (15 to 35ºC)

    ±1.5ºC (-10 to 15ºC and 35 to 50ºC)

•  Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD

●Auxiliary Analog Input

•  Use: Remote setpoint setting, external compensating input, auxiliary input for com-

putation, etc.

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type, instrument range, and measurement accuracy: See the table below.

Input Type

Instrument Range

Accuracy

Standard signal

0.400 to 2.000 V

±0.2% of instrument range ±1 digit

1.000 to 5.000 V

±0.1% of instrument range ±1 digit

DC voltage

0.000 to 2.000 V

±0.2% of instrument range ±1 digit

0.00 to 10.00 V

±0.1% of instrument range ±1 digit

DC voltage 

for high-input 

impedance

0.000 to 1.250 V

±0.1% of instrument range ±1 digit

•  Input sampling (control) period: Same as universal input

•  Input resistance: About 1 MΩ

    However, 10 MΩ or more for DC voltage for high-input impedance range

•  Burnout detection: Functions at standard signal

    Burnout is determined to have occurred if it is 0.1 V or less.

● Universal Input (Optional suffix code: /U1)

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type, instrument range, and measurement accuracy: Same as the standard-

equipped universal input except the table below.

Input Type 

Instrument Range

Accuracy

°C

°F 

4-wire RTD

JPt100

-200.0 to 500.0°C

 -300.0 to 1000.0°F  ±0.5°C of instrument range ±1 digit

-150.00 to 150.00°C  -200.0 to 300.0°F  ±0.2°C of instrument range ±1 digit

Pt100

-200.0 to 850.0°C

 -300.0 to 1560.0°F  ±0.1% of instrument range ±1 digit 

(Note 1)

-200.0 to 500.0°C

 -300.0 to 1000.0°F  ±0.5°C of instrument range ±1 digit

-150.00 to 150.00°C  -200.0 to 300.0°F  ±0.2°C of instrument range ±1 digit

Note 1

: ±0.5°C ±1 digit in the range between -200.0 and 500.0°C/-300.0 and 1000.0°F.

•  Input sampling (control) period: Same as the standard-equipped universal input.

•  Burnout detection: Same as the standard-equipped universal input.

n

 Analog Output Specifications

•  Number of outputs:

    Control output: 1

    Cooling-side control output of Heating/cooling type: 1

•  Output type: Current output or voltage pulse output

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

    The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

 

  and power frequency at 50/60 Hz.

•  Voltage pulse output:

    Use: Time proportional output

    On-voltage: 12 V or more/load resistance of 600 Ω or more

    Off-voltage: 0.1 V DC or less

    Time resolution: 10 ms or 0.1% of output, whichever is larger

n

 Step Response Time Specifications

Within 500 ms (when the control period is 100 ms)

Within 1 s (when the control period is 200 ms)

(63% of analog output response time when a step change of 10 to 90% of input span 

is applied)

n

 Triac Output Specifications

• Contact type and number of output: zero cross; 1 point

Load voltage: 75 to 250 VAC

Allowable load current: 0.8 A when the ambient temperature is 20°C, 0.3 A when the 

ambient temperature is 50°C.

• Minimum load current: 20 mA (*)

*: Unusable for a small load of 10 mA or less.

*: If there is a risk of surge current, connect a current-limiting reactor, a current-

limiting fuse or a breaker in series to the load power supply.

• Use: Time proportional output, Alarm output

• Time resolution of control output: 1/commercial frequency (s) or 0.1% of output, 

whichever is larger.

n

 Relay Contact Output Specifications

•  Contact type and number of outputs:

    Control output: contact point 1c; 1 point

    Cooling-side control output of Heating/cooling type: contact point 1c; 1 point

    Event output: contact point 1a; 3 points (common is independent)

•  Contact rating:

    Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load)

    Contact point 1a (event output): 240 V AC, 1A or 30 V DC, 1 A (resistance load)

•  Use: Time proportional output, event output, alarm output, FAIL output, etc.

•  Time resolution of control output: 10 ms or 0.1% of output, whichever is larger

Note: This cannot be used for a small load of 10 mA or less.

n

 Position Proportional Output Specifications

•  Position signal input:

    Slide resistance: 100 Ω to 2.5 kΩ of total resistance

   

100% side and slide line: with disconnection detection

   

0% side: without disconnection detection

    Current input: 4 to 20 mA (with disconnection detection)

•  Sampling period: 50 ms

•  Measurement resolution: 0.1% of input span

•  Position proportional relay output:

   

Contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)

Note: This cannot be used for a small load of 10 mA or less.

n

 

Retransmission Output Specifications

•  Number of outputs: Retransmission output; 1, shared with 15 V DC loop power 

supply

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

    The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

    and power frequency at 50/60 Hz.

n

 

15 V DC Loop Power Supply Specifications

(Shared with retransmission output)

•  Power supply: 14.5 to 18.0 V DC

•  Maximum supply current: About 21 mA (with short-circuit current limiting circuit)

n

 Contact Input Specifications

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type: No-voltage contact input or transistor contact input

•  Input contact rating: 12 V DC, 10 mA or more

    Use a contact with a minimum on-current of 1 mA or more.

•  ON/OFF detection:

    No-voltage contact input:

   

Contact resistance of 1 kΩ or less is determined as “ON” and contact

   

resistance of 50 kΩ or more as “OFF.”

    Transistor contact input:

   

Input voltage of 2 V or less is determined as “ON” and leakage current must 

   

not exceed 100 µA when “OFF.”

•  Minimum status detection hold time: Control 50 ms

•  Use: PTNO. switch, operation mode switch, and event input

n

 Transistor Contact Output Specifications

•  Number of outputs: See the table of Model and Suffix Codes.

•  Output type: Open collector (SINK current)

•  Output contact rating: Max. 24 V DC, 50 mA

•  Output time resolution: Min. 100 ms

n

 Heater Break Alarm Specifications

•  Number of inputs: 2

•  Number of outputs: 2 (transistor contact output)

•  Use: Measures the heater current using an external current transformer (CT) and 

generates a heater break alarm when the measured value is less than the break 

detection value.

•  Current transformer input resistance: About 9.4 Ω

•  Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be ap-

plied.)

•  Heater current setting range: OFF, 0.1 to 300.0 Arms

    Heater current measured value display range: 0.0 to 360.0 Arms

 

Note: The CT ratio can be set. CT ratio setting range: 1 to 3300

•  Recommended CT: CT from U.R.D., Ltd.

    CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms

    CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms

•  Heater current measurement period: 200 ms

•  Heater current measurement accuracy: ±5% of current transformer input range 

span ± 1digit (CT error is not included.)

•  Heater current detection resolution: Within 1/250 of current transformer input range span

•  Break detection On-time: Min. 0.2 second (for time proportional output)

Summary of Contents for UTAdvanced UP55A

Page 1: ...al area 4 5 CH3 RS485 communication Max 38 4 kbps 2 wire 4 wire CC3 CC Link communication with Modbus master function PD3 PROFIBUS DP communication with Modbus master function DN3 DeviceNet communicat...

Page 2: ...nd measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC vo...

Page 3: ...uit CAUTION When connecting two or more crimp on terminal lugs to the single terminal block bend the crimp on terminal lugs before tightening the screw Note that the wiring of two or more crimp on ter...

Page 4: ...on faulted green red flashing No electricity CHK MNS 1 2 3 4 5 Suffix code Type 3 3 except Type 2 3 CC Link communication with Modbus master RS 485 RSB RSA SG 407 408 409 CC L If the UP is located at...

Page 5: ...stall and wire a controller Monitoring and control of regular operations Adjust PID using auto tuning or manually for PID control Other setup Operation NO NO NO YES YES YES Control mode Single loop co...

Page 6: ...DE menu is displayed ALRM menu is displayed 1 2 3 4 5 Show the Operation Display Hold down the key for 3 seconds Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET...

Page 7: ...between digits Press the Down arrow key until TSP appears Press the Down arrow key Press the Down arrow key 12 Set the segment PID number Segment time 50 minutes 13 Press the SET ENTER key Press the D...

Page 8: ...User s Manual Program Pattern Data parameters for segments Maximum value of PV input range Maximum value of PV input scale Unit A program pattern can be drawn in the right table Minimum value of PV i...

Page 9: ...2 3 4 Show the Operation Display Hold down the PARAMETER key for 3 seconds to display MODE menu Press the SET ENTER key Press the SET ENTER key The parameter HOLD Pause cancel release of program oper...

Page 10: ...g Advance Function Advance can be performed during program operation using any of the following 1 MODE key 2 Parameter 3 Contact input and 4 Communication The following shows an example of switching u...

Page 11: ...mits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 17 Cooling side OUT high limit 18 Cooling side OUT low limit Add 100 for de energized For example when the PV...

Page 12: ...a decimal point position using LL50A Parameter Set ting Software 0 Table below STD Parameter n 01 n 02 n 03 n 04 n 05 n 06 n 07 n 08 n 09 n 10 Pn n 10 segment Linearizer 1 2 Setting Parameter Menu sym...

Page 13: ...back input error or break occurs 2 Valve position estimating type 0 RTS Retransmission output type of RET OFF Disable PV1 PV SP1 SP OUT1 OUT Valve opening 0 to 100 in Position proportional control LPS...

Page 14: ...DI25 5061 DI26 5062 E3 terminal area DI31 5073 DI32 5074 DI33 5075 DI34 5076 DI35 5077 E4 terminal area DI41 5089 DI42 5090 DI43 5091 DI44 5092 DI45 5093 DI46 5094 OFF STD PN B0 Bit 0 of PID number OF...

Reviews: