IM 05P02C41-15EN page 5/14
Contents
1. Names and Functions of Display Parts
2. Setup Procedure
3. Quick Setting Function (Setting of Input and Output)
4.
Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)
5. Setting Alarm Type
6. Setting Alarm Setpoint
1. Names and Functions of Display Parts
(2) + (3) + (4) : Setpoint display
(1)
(9)
(2)
(10)
(11)
(12)
(13)
(4)
(3)
(5)
(6)
(7)
(8)
No. in figure
Name
Description
(1)
PV display
(white or red)
Displays PV.
Displays an error code if an error occurs.
Displays the scrolling guide in the Menu Display and Parameter
Setting Display when the guide display ON/OFF is set to ON.
(2)
Group display (pattern
number)
(green)
1 to 30 represent pattern numbers in the Operation Display.
Displays a group number (1 to 8 or R) and terminal area (E1 to E4)
in the Parameter Setting Display.
(3)
Symbol display (orange) Displays a parameter symbol.
(4)
Data display (orange) Displays a parameter setpoint and menu symbol.
(5)
Bar-graph display
(event, alarm)
(orange)
Displays the event status and the segment position in the Operation
Display. (Default values: Time event status, Alarm status)
Displays control output value (OUT) and measured input value (PV).
The data to be displayed can be set by the parameter.
(6)
Event indicator
(orange)
Lit when the PV events occur.
Event displays can be set by the parameter.
(7)
Key navigation indica-
tor (green)
Lit or blinks when the Up/Down or Left/Right arrow key operation
is possible.
(8)
Parameter display level
indicator (green)
Displays the setting conditions of the parameter display level func-
tion.
Parameter display level
EASY
PRO
Easy setting mode
Lit
Unlit
Standard setting mode
Unlit
Unlit
Professional setting mode
Unlit
Lit
(9)
Program monitor
(green)
Displays the status of increment, constancy, and decrement of the
program setpoint.
: Lit when a program setpoint is increasing.
: Lit when a program setpoint is constant.
: Lit when a program setpoint is decreasing.
(10)
Status indicator
(green and red)
Displays the operating conditions and control status.
Indicator
Description
HLD
Lit when in hold mode (HLD).
CAS
Lit when in cascade mode (CAS).
PRG
Lit when in program operation mode (PRG).
Lit while the Starting time of program operation
(S.TM) is available.
RST
Lit when in reset mode (RST).
MAN
Lit when in manual mode (MAN).
Blinks during auto-tuning.
(11)
Security indicator (red) Lit if a password is set. The setup parameter settings are locked.
(12)
Ladder operation
indicator (green)
Lit while the ladder program operation is executed.
(13)
Loop 2 indicator
(LP2 lamp)
(green)
Lit when the control mode is Cascade control.
In the Operation Display, the LP2 lamp is lit while the Loop-2 data
is displayed on Setpoint display.
In the Parameter Setting Display, the LP2 lamp indicates the
loop of displayed menu symbol or parameter symbol. The LP2
lamp is lit while the Loop-2 menu symbol or parameter symbol is
displayed.
(4)
(5)
(1)
(2)
(3)
No. in figure
Name
Description
(1)
DISPLAY key
Used to switch the Operation Displays.
Press the key in the Operation Display to switch the provided
Operation Displays.
Press the key in the Menu Display or Parameter Setting Display
to return to the Operation Display.
(2)
PARAMETER key
Hold down the key for 3 seconds to move to the Operation
Parameter Setting Display.
Hold down the key and the Left arrow key simultaneously for 3
seconds to move to the Setup Parameter Setting Display.
Press the key in the Parameter Setting Display to return to the
Menu Display. Press the key once to cancel the parameter set-
ting (setpoint is blinking).
(3)
SET/ENTER key
Up/Down/Left/Right
arrow keys
SET/ENTER key
Press the key in the Menu Display to move to the Parameter
Setting Display of the Menu. Press the key in the Parameter
Setting Display to transfer to the parameter setting mode
(setpoint is blinking), and the parameter can be changed.
Press the key during parameter setting mode to register the
setpoint.
Up/Down/Left/Right arrow keys
Press the Left/Right arrow keys in the Menu Display to switch
the Displays.
Press the Up/Down/Left/Right arrow keys in the Parameter
Setting Display to switch the Displays.
Press the Up/Down arrow keys during parameter setting mode
(setpoint is blinking) to change a setpoint.
Press the Left/Right arrow keys during parameter setting mode
(setpoint is blinking) to move between digits according to the parameter.
(4)
Light-loader interface
It is the communication interface for the adapter cable used when
setting and storing parameters from a PC. The LL50A Parameter
Setting Software (sold separately) is required.
(5)
RUN key
RST key
MODE key
PTN key
RUN key: Press the RUN key for 1 second while an operation
display is shown starts the program pattern operation.
RST key: Press the RST key for 1 second while an operation
display is shown stops the program pattern operation.
MODE key: Presents a display for switching between the HOLD,
ADVANCE, PROG, RESET, LOCAL, REMOTE and
AUTO/MAN. In order to change the operation mode,
press the SET/ENTER key while the setpoint is blinking.
PTN key: A program pattern number can be selected during the
operation except the program pattern operation. (The
program pattern number displayed on the Group display
blinks.) When the PTN key is pressed while the program
pattern number is blinking, the blinking stops.
Users can assign functions to the key using parameters.
Note: The communication connector (maintenance port) for LL50A Parameter Setting Software is
on the top of the unit.
2. Setup Procedure
The following flowchart shows the setup procedure for UP55A.
Install and wire a controller.
Monitoring and control of regular operations
Adjust PID using auto-tuning or manually for PID control.
Other setup
Operation
NO
NO
NO
YES
YES
YES
Control mode: Single-loop control only
Set the other parameters as needed.
Programming
Set the program pattern.
PID tuning
Input setup
Output setup
Installation
and wiring
Power ON
Control mode setup
Control type setup
Control type setup
Input/output setup
Valve position
adjustment
Use
Quick setting
function?
Position
proportional
type?
Position
proportional
type?
For Position proportional type
3. Quick Setting Function (Setting of Input and Output)
The Quick setting function is a function to easily set the basic function of the control-
ler.
Turn on the controller to start the Quick setting function.
This function allows you to easily set the control type, input, and output, and quickly
start the control action.
The items (parameters) to be set by Quick setting function are as follows.
(1) Control type (PID control, Heating/cooling control, etc.)
(2) Input function (PV input type, range, scale (at voltage input), etc.)
(3) Output function (control output type and cycle time)
After turning on the controller, first decide whether or not to use the Quick setting func-
tion.
The Quick setting function can be used only when the control mode is Single-loop
control. For other control modes, set the functions without using the Quick setting
function.
Operation in Initial Display
· Press the SET/ENTER key while YES is displayed to start the Quick setting function.
· If you change YES to NO and press the SET/ENTER key, Operation Display will
appear without starting the Quick setting function.
Operation
Guide
Initial Settings
This operation guide describes basic settings and operations of the UP55A.
For details of each function, see User’s Manual.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the MODE key.
UP55A
Program Controller
Operation Guide for Single-loop Control
Operation for Setting
· To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.
· To change and set the parameter setting, press the SET/ENTER key to start the
setpoint blinking. The blinking state allows you to make changes (setting mode).
Use the Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/EN-
TER key to register the setting.
■
Making Settings Using Quick Setting Function
Example: Setting to PID control, thermocouple type K (range of 0.0 to
500.0
0
C), and current control output
For the detailed procedure and switching of displays, see "Flow of Quick Setting
Function" below. For the parameters to set, see the next page.
(1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.
(2) Set the control type parameter (CNT) to PID (PID control).
(3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0
0
C).
(4) Set the PV input unit parameter (UNIT) to C (Degree Celsius).
(5) Set the maximum value of PV input range parameter (RH) to 500.0.
(6) Set the minimum value of PV input range parameter (RL) to 0.0.
(7) Set the output type selection parameter (OT) to OUT terminals (current).
(8) Finally, EXIT is displayed. Change NO to YES and press the SET/ENTER key to
complete the setup. Operation Display appears.
■ Flow of Quick Setting Function
In Quick setting mode, the parameter guide appears on PV display.
This guide can be turned on/off with the MODE key.
First, the control type parameter
(CNT) is displayed.
Initial value: PID (PID control)
H/C (Heating/cooling control) for
Heating/cooling type unit.
The PV input type
parameter (IN) is
displayed.
Initial value: OFF
OFF blinks.
Blinking allows you to
change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum
value of PV input range) has been
changed to 500.0.
The setpoint for the parameter
RH has been registered.
The PV input unit parameter
(UNIT) is displayed.
Initial value: C (Degree
Celsius)
Press the SET/ENTER key
while YES is displayed to start
the Quick setting.
Select NO with the Down
arrow key and press the
SET/ENTER key.
Select NO to return to
the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
The upper limit value of the
setting range is displayed for the
parameter RH (maximum value
of PV input range).
Change the setpoint using the Up/Down
arrow keys to increase and decrease the
value and the Left/Right arrow keys to
move between digits.
Finally, EXIT is displayed.
Press the SET/ENTER key to swtich to the setting mode.
Change NO to YES and press the SET/ENTER key to
complete the setup of the basic function.
Operation Display appears.
The Quick setting function continues in the NO state.
Displays the measured
input value (PV).
Displays the starting
target setpoint (SSP).
Follow the same procedure to set RL to 0.0 and
OT to 00.02.
Set other parameters as needed.
Quick setting starts
Power-on
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
12.
7.
[YES]
Operation Display
[NO]
First, the control type parameter
(CNT) is displayed.
Initial value: PID (PID control)
H/C (Heating/cooling control) for
Heating/cooling type unit.
The PV input type
parameter (IN) is
displayed.
Initial value: OFF
OFF blinks.
Blinking allows you to
change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum
value of PV input range) has been
changed to 500.0.
The setpoint for the parameter
RH has been registered.
The PV input unit parameter
(UNIT) is displayed.
Initial value: C (Degree
Celsius)
Press the SET/ENTER key
while YES is displayed to start
the Quick setting.
Select NO with the Down
arrow key and press the
SET/ENTER key.
Select NO to return to
the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
The upper limit value of the
setting range is displayed for the
parameter RH (maximum value
of PV input range).
Change the setpoint using the Up/Down
arrow keys to increase and decrease the
value and the Left/Right arrow keys to
move between digits.
Finally, EXIT is displayed.
Press the SET/ENTER key to swtich to the setting mode.
Change NO to YES and press the SET/ENTER key to
complete the setup of the basic function.
Operation Display appears.
The Quick setting function continues in the NO state.
Displays the measured
input value (PV).
Displays the starting
target setpoint (SSP).
Follow the same procedure to set RL to 0.0 and
OT to 00.02.
Set other parameters as needed.
Quick setting starts
Power-on
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
12.
7.
[YES]
Operation Display
[NO]