IM 05P02C41-15EN  page 1/14

Contents

1.  Safety Precautions

2.  Model and Suffix Codes

3.  How to Install

4.  Hardware Specifications

5.  How to Connect Wires

6.  Terminal Wiring Diagrams

Introduction

Thank you for purchasing the UP55A Program Controller.

This operation guide describes the basic operations related to the single-loop control 

function of the UP55A. The guide should be provided to the end user of this product.

Be sure to read this operation guide before using the product in order to ensure 

correct operation.

For details of each function, refer to User’s Manual. Before using the product, refer 

to the table of Model and Suffix Codes to make sure that the delivered product is 

consistent with the model and suffix codes you ordered. Also make sure that the 

following items are included in the package.

• Program Controller (the model you ordered)

 ..........................................

x1

• Set of Brackets ........................................................................................

x1

• Unit Label (L4502VZ)

 ..............................................................................

x1

• Tag Label (L4502VE)

 ..............................................................................

x1

  (Only when ordered.)

• Terminal Cover (L4502XP)

 .....................................................................

x1

Target Readers

This guide is intended for the following personnel;

•  Engineers responsible for installation, wiring, and maintenance of the equipment.

•  Personnel responsible for normal daily operation of the equipment.

1.  Safety Precautions

The following symbol is used on the instrument. It indicates the possibility of injury 

to the user or damage to the instrument, and signifies that the user must refer to 

the user’s manual for special instructions. The same symbol is used in the user’s 

manual on pages that the user needs to refer to, together with the term “WARNING” 

or “CAUTION.”

WARNING 

Calls attention to actions or conditions that could cause serious 

or fatal injury to the user, and indicates precautions that should be 

taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to 

the user or damage to the instrument or property and indicates pre-

cautions that should be taken to prevent such occurrences.

AC

AC/DC

 

The equipment wholly protected by double insulation or reinforced insulation.

  

Functional grounding terminals 

   

(Do not use this terminal as a protective grounding terminal).

Note

Identifies important information required to operate the instrument.

n

 Warning and Disclaimer

(1) YOKOGAWA makes no warranties regarding the product except those stated in 

the WARRANTY that is provided separately.

(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to 

any person or entity for any loss or damage, direct or indirect, arising from the 

use of the product or from any unpredictable defect of the product.

n

 Safety, Protection, and Modification of the Product

(1) In order to protect the system controlled by this product and the product itself, 

and to ensure safe operation, observe the safety precautions described in the 

user’s manual. Use of the instrument in a manner not prescribed herein may 

compromise the product's functions and the protection features inherent in the 

device. We assume no liability for safety, or responsibility for the product's quality, 

performance or functionality should users fail to observe these instructions when 

operating the product.

(2) Installation  of  protection  and/or  safety  circuits  with  respect  to  a  lightning 

protector; protective equipment for the system controlled by the product and the 

product itself; foolproof or failsafe design of a process or line using the system 

controlled by the product or the product itself; and/or the design and installation 

of other protective and safety circuits are to be appropriately implemented as the 

customer deems necessary.

(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts 

or consumables.

(4) This product is not designed or manufactured to be used in critical applications 

that directly affect or threaten human lives. Such applications include nuclear 

power  equipment,  devices  using  radioactivity,  railway  facilities,  aviation 

equipment, air navigation facilities, aviation facilities, and medical equipment. 

If so used, it is the user’s responsibility to include in the system additional 

equipment and devices that ensure personnel safety.

(5) Modification of the product is strictly prohibited.

(6) This product is intended to be handled by skilled/trained personnel for electric 

devices.

(7) This  product  is  UL  Recognized  Component.  In  order  to  comply  with  UL 

standards, end-products are necessary to be designed by those who have 

knowledge of the requirements.

WARNING 

Power Supply

  Ensure that the instrument’s supply voltage matches the voltage 

of the power supply before turning ON the power.

l

  Do Not Use in an Explosive Atmosphere

  Do not operate the instrument in locations with combustible 

or explosive gases or steam. Operation in such environments 

constitutes an extreme safety hazard. Use of the instrument in 

environments with high concentrations of corrosive gas (H

2

S, 

SO

X

, etc.) for extended periods of time may cause a failure.

l

  Do Not Remove Internal Unit

  The internal unit should not be removed by anyone other than 

YOKOGAWA's service personnel. There are dangerous high 

voltage parts inside. Additionally, do not replace the fuse by 

yourself.

l

  Damage to the Protective Construction

  Operation of the instrument in a manner not specified in the 

user’s  manual may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-

ment this product may cause radio interference in which case the 

user needs to take adequate measures.

2.  Model and Suffix Codes

n

 UP55A

[Style:S2]

Model

Suffix code

Optional

suffix

code

Description

UP55A

Program Controller (provided with 3 DIs, and 3 DOs) 

(Power supply: 100-240 V AC)

30 program patterns / 300 program segments (Max. 99 

segments per pattern)

Fixed code

-NNN

Always "-NNN”

Display language (*1)

-1

English

-2

German

-3

French

-4

Spanish

Case color 

0

White (Light gray)

1

Black (Light charcoal gray)

Output 1 (*2) (*3)

-A

Analog output (current/voltage pulse)

-R

Relay output (c-contact)

-U

Universal output (current/voltage pulse/relay)

-T

Triac output

-P

Position proportional output

Output 2 (*2) (*3)

A

Analog output (current/voltage pulse)

R

Relay output (c-contact)

U

Universal output (current/voltage pulse/relay)

T

Triac output

N

None

Retransmission output

/RT

Retransmission output or 15 V DC power supply

Heater break alarm (*3)

/HA

Heater break alarm

E1 terminal area (*4)

/R1

Remote (1 additional aux. analog) input and 1 additional DI

/U1

1 additional universal input (TC/RTD/DCV/mA)

/X1

5 additional DIs

/Y1

5 additional DOs

/W1

2 additional DIs and 2 additional DOs

E2 terminal area (*4)

/A2

1 additional aux. analog input and 1 additional DI

/X2

5 additional DIs

/Y2

5 additional DOs

/W2

2 additional DIs and 2 additional DOs

E3 terminal area (*4) (*5)

/CH3

RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)

/CC3

CC-Link communication(with Modbus master function)

/PD3

PROFIBUS-DP communication (with Modbus master function)

/DN3

DeviceNet communication (with Modbus master function)

/ET3

Ethernet communication (with serial gateway function)

/X3

5 additional DIs

/Y3

5 additional DOs

/W3

2 additional DIs and 2 additional DOs

E4 terminal area (*4) (*5)

/A4

1 additional aux. analog input and 1 additional DI

/C4

RS485 communication (Max. 19.2 kbps, 2-wire/4-wire)

/L4

24 V DC loop power supply

/AC4

1 additional aux. analog input, 1 additional DI, and 

RS485 communication (Max.19.2 kbps, 2-wire)

/LC4

24 V DC loop power supply and RS485 communication 

(Max.19.2 kbps, 2-wire)

/X4

5 additional DIs

/Y4

5 additional DOs

/W4

2 additional DIs and 2 additional DOs

Power supply

/DC

Power supply 24 V AC/DC

Additional treatment (*6)

/CT

Coating

*1: 

English, German, French, and Spanish can be displayed as the guide display.

*2: 

For heating/cooling output, both Output 1 and Output 2 should be specified. Not available 

when Output 2 is “N”. For position proportional output, specify “-P” for Output 1 and “N” for Output 2. 

*3: 

The /HA option can be specified only when the code for Output 1 and 2 is “-AN”, “-RN”, “-UN” or “-TN.” 

*4: 

Only one option is available for each terminal area of E1 to E4.

*5: 

The /L4 and /LC4 options for E4 terminal area can be specified only when the E3 terminal 

area option is not specified or specified any of /CH3, /X3, /Y3 or /W3.

*6: 

When the /CT option is specified, the UT55A does not conform to the safety standards (UL 

and CSA) and CE marking.

n

 Accessories (sold separately)

The following is an accessory sold separately.

•  LL50A Parameter Setting Software

Model

Suffix code

Description

LL50A

-00

Parameter Setting Software

•  Set of Brackets (Part number: L4502TP)

 

2 pcs for upper and lower sides

• User’s Manual (A4 size)

 

Note: User’s Manual can be downloaded from a website.

•  User’s Manual (CD-ROM), Model: UTAP003

 

Note: Contains all manuals.

•  Operation Guide for Single-loop Control (this document) x7 (A3 size)

 

(Installation and Wiring, Initial Settings, Programmings, Operations, and Parameters)

3.  How to Install

n

 Installation Location

The  instrument  should  be  installed  in  indoor  locations  meeting  the  following 

conditions:

•  Instrumented panel

  This instrument is designed to be mounted in an instrumented panel. Mount the 

instrument in a location where its terminals will not inadvertently be touched.

•  Well ventilated locations

  Mount the instrument in well ventilated locations to prevent the instrument’s inter-

nal temperature from rising. 

  However, make sure that the terminal portions are not exposed to wind. Exposure 

to wind may cause the temperature sensor accuracy to deteriorate. To mount mul

-

tiple indicating controllers, see the external dimensions/panel cutout dimensions 

which follow. If mounting other instruments adjacent to the instrument, comply with 

these panel cutout dimensions to provide sufficient clearance between the instru-

ments.

•  Locations with little mechanical vibration

  Install the instrument in a location subject to little mechanical vibration.

•  Horizontal location

  Mount the instrument horizontally and ensure that it is level, with no inclination to 

the right or left.

Front panel

of controller

Keep this angle

within 30°

Rear of

controller

30°

Note

If the instrument is moved from a location with low temperature and low humidity 

to a place with high temperature and high humidity, or if the temperature changes 

rapidly, condensation will result. Moreover, in the case of thermocouple inputs, 

measurement errors will result. To avoid such a situation, leave the instrument in the 

new environment under ambient conditions for more than 1 hour prior to using it.

Do not mount the instrument in the following locations:

•  Outdoors

•  Locations subject to direct sunlight or close to a heater

  Install the instrument in a location with stable temperatures that remain close to an 

average temperature of 23°C. Do not mount it in locations subject to direct sunlight 

or close to a heater. Doing so adversely affects the instrument.

•  Locations with substantial amounts of oily fumes, steam, moisture, dust, or 

corrosive gases

  The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely 

affects the instrument. Do not mount the instrument in locations subject to any of 

these substances.

•  Areas near electromagnetic field generating sources

  Do not place magnets or tools that generate magnetism near the instrument. If the 

instrument is used in locations close to a strong electromagnetic field generating 

source, the magnetic field may cause measurement errors.

•  Locations where the display is difficult to see

  The instrument uses an LCD for the display unit, and this can be difficult to see 

from extremely oblique angles. Mount the instrument in a location where it can be 

seen as much as possible from the front.

•  Areas close to flammable articles

  Absolutely do not place the instrument directly on flam-

mable surfaces. If such a circumstance is unavoidable 

and the instrument must be placed close to a flammable 

item, provide a shield for it made of 1.43 mm thick plated 

steel or 1.6 mm thick unplated steel with a space of at 

least 150 mm between it and the instrument on the top, 

bottom, and sides.

•  Areas subject to being splashed with water

WARNING 

Be sure to turn OFF the power supply to the controller before in-

stalling it on the panel to avoid an electric shock.

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATION

Network Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN

YOKOGAWA CORPORATION OF AMERICA

Head office and for product sales

2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.

Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

150 mm

150 mm

150 mm

150 mm

150 mm

150 mm

150 mm

150 mm

Operation

Guide

IM 05P02C41-15EN

UP55A

Program Controller

Operation Guide for Single-loop Control

This operation guide describes installation, wiring, and other tasks required to make the 

controller ready for operation.

2nd Edition : Jan. 2011

Installation and Wiring

n

 Waste Electrical and Electronic Equipment (WEEE), 

Directive 2002/96/EC

This is an explanation of how to dispose of this product based on Waste Electrical and 

Electronic Equipment (WEEE), Directive 2002/96/EC. This directive is only valid in the EU.

Marking

This  product  complies  with  the  WEEE  Directive  (2002/96/EC) 

marking requirement.

This marking indicates that you must not discard this electrical/

electronic product in domestic household waste.

Product Category

With  reference  to  the  equipment  types  in  the  WEEE  directive  Annex  1,  this 

product  is  classified  as  a  “Monitoring  and  Control  instrumentation”  product.

 

Do not dispose in domestic household waste. When disposing products in the EU, 

contact your local Yokogawa Europe B.V. office.

Summary of Contents for UTAdvanced UP55A

Page 1: ...al area 4 5 CH3 RS485 communication Max 38 4 kbps 2 wire 4 wire CC3 CC Link communication with Modbus master function PD3 PROFIBUS DP communication with Modbus master function DN3 DeviceNet communicat...

Page 2: ...nd measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC vo...

Page 3: ...uit CAUTION When connecting two or more crimp on terminal lugs to the single terminal block bend the crimp on terminal lugs before tightening the screw Note that the wiring of two or more crimp on ter...

Page 4: ...on faulted green red flashing No electricity CHK MNS 1 2 3 4 5 Suffix code Type 3 3 except Type 2 3 CC Link communication with Modbus master RS 485 RSB RSA SG 407 408 409 CC L If the UP is located at...

Page 5: ...stall and wire a controller Monitoring and control of regular operations Adjust PID using auto tuning or manually for PID control Other setup Operation NO NO NO YES YES YES Control mode Single loop co...

Page 6: ...DE menu is displayed ALRM menu is displayed 1 2 3 4 5 Show the Operation Display Hold down the key for 3 seconds Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET...

Page 7: ...between digits Press the Down arrow key until TSP appears Press the Down arrow key Press the Down arrow key 12 Set the segment PID number Segment time 50 minutes 13 Press the SET ENTER key Press the D...

Page 8: ...User s Manual Program Pattern Data parameters for segments Maximum value of PV input range Maximum value of PV input scale Unit A program pattern can be drawn in the right table Minimum value of PV i...

Page 9: ...2 3 4 Show the Operation Display Hold down the PARAMETER key for 3 seconds to display MODE menu Press the SET ENTER key Press the SET ENTER key The parameter HOLD Pause cancel release of program oper...

Page 10: ...g Advance Function Advance can be performed during program operation using any of the following 1 MODE key 2 Parameter 3 Contact input and 4 Communication The following shows an example of switching u...

Page 11: ...mits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 17 Cooling side OUT high limit 18 Cooling side OUT low limit Add 100 for de energized For example when the PV...

Page 12: ...a decimal point position using LL50A Parameter Set ting Software 0 Table below STD Parameter n 01 n 02 n 03 n 04 n 05 n 06 n 07 n 08 n 09 n 10 Pn n 10 segment Linearizer 1 2 Setting Parameter Menu sym...

Page 13: ...back input error or break occurs 2 Valve position estimating type 0 RTS Retransmission output type of RET OFF Disable PV1 PV SP1 SP OUT1 OUT Valve opening 0 to 100 in Position proportional control LPS...

Page 14: ...DI25 5061 DI26 5062 E3 terminal area DI31 5073 DI32 5074 DI33 5075 DI34 5076 DI35 5077 E4 terminal area DI41 5089 DI42 5090 DI43 5091 DI44 5092 DI45 5093 DI46 5094 OFF STD PN B0 Bit 0 of PID number OF...