25
IM 77C01E31-01EN
SFLC-212-181
25
Setting mode 2. Function table (1)
Setting
No.
Function
Functional description
Default setting
Important
setting
Page
211
Voltage range
Sets the voltage-measurement range
(primary voltage).
3φ3W
6600V (
8
)
✓
43
to 46
1φ3W
110.0V
1φ2W
3300V
(
8
)
212
Digit number of voltage
range
Sets the digit number of voltage range.
3φ3W
4 digits
43
to 46
1φ3W
4 digits
1φ2W
4 digits
213
Current range
Sets the current-measurement range
(primary current).
3φ3W
100.0A
✓
43
to 46
1φ3W
500.0A
1φ2W
50.00A
214
Current display
intrinsic sensitivity
Sets the full scale of current meter.
3φ3W
100.0A
43
to 46
1φ3W
500.0A
1φ2W
50.0A
215
Digit number of current
range
Sets the digit number of current range.
3φ3W
4 digits
43
to 46
1φ3W
4 digits
1φ2W
4 digits
216
Active power polarity
Sets the deflection display of active power
meter.
One-way deflection
43
to 46
217
Active power range
Sets the full scale of active power meter.
3φ3W
1200k
W
(
9
)
43
to 46
1φ3W
100.0kW
1φ2W
150.0kW
(
10
)
218
Digit number of active
power range
Sets the digit number of active power
range.
3φ3W
4 digits
43
to 46
1φ3W
4 digits
1φ2W
4 digits
219
Reactive power range
Sets the full scale of reactive power meter.
3φ3W
600.0kvar (
9
)
43
to 46
1φ3W
50.00kvar
1φ2W
75.00kvar (
10
)
21A
Digit number of reactive
power range
Sets the digit number of reactive power
range.
3φ3W
4 digits
4
3
to 46
1φ3W
4 digits
1φ2W
4 digits
21B
Power-factor range
Sets the full scale of power-factor meter. 0.5 to 1 to 0.5
43
to 46
21C
Frequency range
Sets the full scale of frequency meter.
45.0 to 65.0Hz
43
to 46
21D
Digit number of
frequency range
Sets the digit number of frequency range.
3 digits
43
to 46
221C
Address
Set the address of device in
communication output.
1
✓
47
222C
Transmission rate
Set the transmission rate of
communication output.
9600bps
✓
47
223C
Parity
Set the parity bit added to communication
data.
Even number
✓
47
224C
Stop bit
Set the stop bit added to communication
data.
1 bit
✓
47
231P
Pulse output factor
Sets the factor of pulse output.
Wh
✓
48
232P
(
11
)
Pulse unit
Sets the pulse unit of pulse output.
3φ3W
10kW
h/pulse
48
1φ3W
1φ2W
1kWh/pulse
Note(
8
)
It is set to “220
.0V (4-digits)
” in 220V input.
Note(
9
) It is set to "40.00kW (4-digits)
" and "20.00kvar
(4-digits)
" in 220V input
.
Note(
10
) It is set to "10.00kW (4-digits)" and "5.000kvar (4-digits)
" in 220V input.
Note(
11
) It is set to “
0.1kWh/pulse” in 220V input.
(3φ3W, 1φ2W)