2-6
<Toc> <Ind>
<2. Setup>
IM 77C01E01-10E
2.2
Setting Communication Conditions
This section describes the setting parameters for using the communication func-
tions, and the setting ranges. For details of setting method, refer to the PR300
Power and Energy Meter User’s Manual (electronic manual).
2.2.1
Conditions for RS-485 Communication
This subsection describes the setting parameters for using the RS-485 communication
function, and the setting ranges.
Table 2.1 Parameters to be Set for Communication Functions
Parameter Name
Protocol
(COMM)
(ST-NO)
(RS-485
communication)
(B-RT)
(PRI)
(STP)
(DLN)
PC link without checksum
2400 bps
9600 bps
19200 bps
1
2
7
8
(NONE)
(EVEN)
(ODD)
(PCLK1)
(PCLK2)
(M ASC)
(M RTU)
(M TCP)
(PR201)
Parameter Symbol
Menu
Setting Range
Initial
Value
Baud rate
Parity*
3
Stop bit*
3
Data length*
2
*
3
Station number
9600
NONE
1
8
01
PCLK2
PC link with checksum
Modbus/ASCII
Modbus/RTU
Modbus/TCP*
1
PR201 original
01 to 99 (01 to 31 recommended)
None
Even
Odd
*1:
Modbus/TCP can be selected for the PR300 with Ethernet communication function only.
*2:
When Modbus /RTU is selected for the protocol, select 8 for the data length. If 7 is selected for the data length,
communication is not possible.
*3:
When PR201 original is selected for the protocol, select NONE for the parity, 1 for the stop bit and 8 for the data length.