<Toc> <Ind>
<8. PR201 Original Communication Protocol>
8-5
IM 77C01E01-10E
8.5
Command Details
■
Command: DG
●
Parameter: 0 (Reads measured values in batch)
• Function
This command reads the active energy, optional electric energy (previous and current
values), active power, voltage-1, current-1 and the power factor.
• Command/response
Number
of bytes
1
2
1
2
2
1
1
Command
element
STX
DG
0
Station
number
(ADR)
Checksum ETX
CR
There is no command data for data reading.
1
2
1
2
5
5
5
Response
element
STX
DG
0
Station
number
(ADR)
ⵧⵧⵧⵧⵧ
Active energy
9
ⵧ
.
ⵧⵧⵧ
E
䊊
(Active power)
ddddd
(Previous
optional
electric
energy value)
ddddd
(Current
optional
electric
energy value)
Number
of bytes
Response data is returned as a 46-byte ASCII character string.
Continued:
8
8
2
1
1
ⵧ
.
ⵧⵧⵧ
E
䊊
(Voltage-1)
ⵧ
.
ⵧⵧⵧ
E
䊊
(Current-1)
6
䉭ⵧ
.
ⵧⵧⵧ
(Power factor)
Checksum ETX
CR
• Example
The PR300 measured values of station number 01 are read out in a batch.
䊐䊐
indicates
the checksum value.
[Command]
[STX]DG001
䊐䊐
[ETX][CR]
The following response is returned for the above command.
[Response]
[STX]DG001100001001.000E+31.000E+31.000E+3G0.800
䊐䊐
[ETX][CR]
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(1) Active energy: 10000 kWh, (2) Optional electric energy (previous value):
10000 Wh, (3) Optional electric energy (current value): 10000 Wh, (4) Active
power: +1.000E+3 W (10000 W), (5) Voltage-1: 1.000E+3 V (1000 V),
(6) Current-1: 1.000E+3 A (1000 A) and (7) Power factor: G0.800.