< 2. Installation, Piping and Wiring >
2-6
IM 12B07N01-01E
[Model PH8MV Solenoid Valve]
Pilot kick operated, 2-port valve. Open when energized.
Fluid:
Normal tap water, industrial water, or air.
Operating Pressure:
0 to 1 MPa
Forward (reverse) Pressure Resistance:
2 MPa
Fluid Temperature:
Water; 5 to 60°C, Air; -10 to 60°C
Cv:
4.5
Process Connection:
Rc 1/2
Power Supply:
100/110/200/220 V AC, 50/60 Hz
Power Consumption:
10 W
Construction:
IP53
Material:
Body; Bronze
Sealing; Nitrile rubber
Ambient Temperature:
Maximum 50°C
Cable Inlet Connection:
G 1/2
Weight:
Approx. 0.9 kg
[Model PH8MVF Explosionproof Solenoid Valve]
Pilot kick operated, 2-port valve. Open when energized.
Fluid:
Normal tap water, industrial water, or air.
Operating Pressure:
0.05 to 1 MPa
Forward (reverse) Pressure Resistance
: 1.5 MPa
Fluid Temperature:
Water; 5 to 60°C, Air; -10 to 60°C
Cv:
4.5
Process Connection:
Rc 1/2
Power Supply:
100V AC, 50/60 Hz., 110V AC, 60 Hz
200V AC, 50/60 Hz., 220V AC, 60 Hz
Power Consumption:
10 W
Construction:
TIIS flameproof (for d2G4 gas).
Material:
Body; Bronze
Seal; Nitrile rubber
Ambient Temperature:
Maximum 50°C
Valve Seat Leakage:
300 Nml/min. (At air pressure 50 to 700 kPa )
Cable Inlet Connection:
G 1/2 (Frameproof packing adaptor)
Mounting Position:
Vertical mounting with coil in top
Weight:
Approx. 1.9 kg