1-23
IM 04P01B01-01E
Functional Explanation and Setup Guide
For the procedure to set the functions, see section 1.10, “Function Setup Guide.”
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
• Switching between Start Printout and Start printout 2, and between End
printout and End printout 2
With the remote control function (/R1 option), you can change the items that are
printed out.
For example, when a process ends successfully, End printout is performed and the
lot number is updated. If the process fails, you can have End printout 2 be carried out
and the lot number remain not updated.
Depending on the status of the “batch comment switching signal,” the following
switches occur when the “record start/stop signal” switches:
Record Start/Stop Signal Status
Batch Comment Switching Signal Status
Level: 0 (Open)
Level: 1 (Closed)
Upon start Edge (rising)
Start printout
Start printout 2
Upon stop Edge (falling)
End printout
End printout 2
Record start/stop
signal
Remote Control Signal
Batch comment
switching signal
Start
Stop
Concluded
successfully
Concluded
unsuccessfully
Start printout
End printout
Start
Stop
Start printout End printout 2
Message Printout Including Measured Values*
Following the specified message format, the date/time, message strings of the standard
function (5 strings of up to 16 characters), and measured instantaneous values* are
printed out together.
• Up to 5 messages of 35 characters can be entered.
• Messages are printed out in the order in which they are set.
• Message strings set with the standard function are specified as the first n number
of characters from the start of the string. If a number of characters is specified more
than once, the first instance is n number of characters from the start of the string, the
second instance is n number of characters immediately after the first instance, and so
on. And, for example, the character string set for message 1 can only be used once
for message format 1.
06/30 10:10 Process-1 134.8°C
Measured value
*
on CH1 (no units)
Character string set for message 1
of the standard function
Date/time
Message Example
* Computed values can also be included on models with the /M1 option.
<Related Topics>
Setting the header printout: Sections 7.24 and 6.14
Assigning functions to the remote control input terminals: Section 7.18
Setting the message string: Section 6.8
Enabling the message format: Section 7.24
Setting the message format: section 6.15
SD Memory Card (/EM1 option)
Measured data can be saved to an SD memory card, and the data can be replayed
on a chart paper (dot model only). The saved data can be used in the YOKOGAWA’s
Universal Viewer. In addition, recorder setup data can be saved to or loaded from an SD
memory card. The setup data can be edited using the RXA10 Configuration Software.
See the
μR10000/μR20000 SD Memory Card (/EM1 option) User’s Manual
, IM 04P01B01-03E.
1.4 Recording