Functional Explanation and Setup Guide
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
Item
Description
Reference
Section
Moving average (dot model)
Use
Moving_AVE
in Basic Setting mode and select Use or Not.
7.11
If Use is selected, set the number of samples of moving average using
Aux >
Moving_AVE
in Setting mode.
6.3
If Not is selected, the
Aux > Moving_AVE
item does not appear.
Integration time of the A/D converter
7.2
Use
A/D
in Basic Setting mode to set the integration time of the A/D converter.
Temperature Unit
Select the temperature unit using
Temperature
in Basic Setting mode.
7.25
Alarm functions
Item
Description
Reference
Section
Alarms for each channel
Use
Alarm
in Setting mode.
5.2
Delay high limit alarm/delay low limit alarm
• Alarm type
7.15
Use
Personalize > Add function > Alarm delay
in Basic Mode and select Use or
Not.
If Use is selected, delay high limit alarm (T) and delay low limit alarm (t) become
selectable under
Alarm > Type
in Setting mode.
5.2
If Not is selected, alarm delay cannot be selected.
• Alarm delay time
6.10
Use
Aux > Alm delay T
in Setting mode to set the alarm delay time.
High limit on rate-of-change alarm/low limit on rate-of-change alarm
Use
Alarm
in Setting mode and set the channel to rate-of-change alarm.
5.2
Use
Alarm > Increase
in Basic Setting mode to set the interval of the high limit on
rate-of-change alarm; use
Alarm > Decrease
in Basic Setting mode to set the interval
of the low limit on rate-of-change alarm.
7.1
Use the alarm ACK operation
• Relay operation and display operation
7.1
Set
Alarm > Behavior
in Basic Setting mode to Hold and set
Alarm > Indicator
to
Hold.
• Executing the alarm ACK operation
3.12
Use
Func > Alarm ACK
in Operation mode to execute the release of the alarm
output.
Set a hysteresis on the alarm occurrence/release value of high limit alarm and low limit alarm
Use
Alarm > Hysteresis
in Basic Setting mode to set the hysteresis to be applied to
the high limit alarm and low limit alarm of measurement channels.
7.1
Likewise, use
Alarm > M_Hysteresis
to set the hysteresis to be applied to the high
limit alarm and low limit alarm of computation channels (/M1 option).
Change the alarm output relay operation
If
Alarm > Act
in Basic Setting mode set to De_energize, alarm output relay is
energized during normal operation and de-energized when an alarm occurs.
7.1
Diagnosis output
Use
Alarm > Diagnosis
in Basic Setting mode to set the function.
7.1
Recording functions
Item
Description
Reference
Section
Chart speed
Use
Chart
in Setting mode to set the chart speed.
5.4
Turn trend recording ON/OFF (dot model)
Use
Aux > Print
out in Setting mode to set whether to trend record on each
measurement channel.
6.6
Change the recording color of measurement channels (dot model).
Use
Color
in Basic Setting mode to set the recording color of measurement channels. 7.5
Record by compensating for the pen offset along the time axis (pen model)
Use
Aux > POC
in Setting mode to turn On/Off offset compensation.
7.6
Record by setting recording zone
Use
Aux > Zone
in Setting mode to set the recording zone for each channel.
6.4
Partial expanded recording Use
Partial
in Basic Setting mode and select Use or Not.
7.13
If Use is selected, set the display mode using
Aux > Partial
in Setting mode.
6.5
If Not is selected, the
Aux > Partial
item does not appear.