<2. General>
2-1
IM 02M04B01-01EN
2. General
2.1 Outline
The MC43 Controller continuously detects the
difference between a process measurement and its
set point, and produces an output air signal that is
a function of this difference and the type of control.
The output signal is transmitted to a control valve or
other control device. The process measurement,
set point, and output signal are indicated on the
controller.
2.2 Standard Specifications
Types of Control:
A1: On-Off
A2: Proportional
A3: Proportional plus Derivative
A4: Proportional plus Integral
A5: Proportional plus Integral plus Derivative
A7: Differential Gap
B4: Batch + Propor Integral
Measurement Range:
See Tables
Control Limits:
Proportional: 4 to 400%
Reset: 0.01 to 50 minutes
Derivative: 0.05 to 50 minutes
Differential Gap: 2 to 100%
Output Signal:
20 to 100 kPa (0.2 to 1.0 kgf/cm
2
) -A2, A3, A4,
A5, B4 Types.
0 kPa or air supply -A1, A7 Types
Air Supply:
140 kPa (1.4 kgf/cm
2
)
Air Consumption:
0.5 Nm
3
/h
Air Connections:
Tapped for JIS Rp1/4 or 1/4 NPT
Ambient Temperature Limits:
−30 to +80°C
Weight:
Approx. 7.6 kg, excluding element and
mounting bracket
Measurement Range:
Element
Code
Standard Span
*2
SI Unit
Metric Unit
psi Unit
PR1
*1
80 kPa
0.8 kgf/cm
2
12 psi
P42
0.1 to 1.37
MPa
1.0 to 14
kgf/cm
2
15 to 200 psi
P51
1.37 to 7 MPa
14 to 70
kgf/cm
2
200 to 1000
psi
P52
7 to 20.6 MPa
71 to 210
kgf/cm
2
1000 to 3000
psi
*1: Pressure range for PR1 is 0.2 to 1 kgf/cm
2
or bar, 20 to
100 kPa, or 3 to 15 psi.
*2: mbar or bar unit calibration is also available.
Element
Standard
Span (°C)
Range Limits
Element
Ambient
Temp.
T1A
25, 50, 100,
150, 200, 250 –25 and 250°C –10 to 66°C
Indicating Accuracy:
PR1, P42, P51, P52 elements
. . . . . . . .
±0.5% of span.
T1A element
. . . . . . . .
±0.5% of span or ±0.3°C
whichever is greater