4.1.1 Link Refresh
Link refresh refers to the reading and writing between the link relays and link
registers in the sequence CPU module and the link data in the FA Link module
attached to a local unit to synchronize the link data in the sequence CPU's data
storage area with that in the FA Link Module.
The sequence CPU reads data from the FA Link Module automatically so that data
communications is transparent.
Link refresh executes concurrently with instruction processing and does not affect
the scan time.
X00501
MOV
$100
X00502
L00033
L00001
W00001
Station 1
Link relay area
Station n
Link register area
Station n
Link relay area
Station n
Link register area
Station 1
Link relay area
Station 1
Link register area
Station n
Link relay area
Station n
Link register area
X00601
MOV
W00001
L00001
L00033
D0001
X00604
X00603
L00003
Station n
Station 1
Station 1
Station n
Link refresh
Link refresh
F0512.VSD
Figure 4.1.2 Link Refresh