3-9
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
■
External Wiring
A two-pair shielded twisted-pair cable is used for wiring of F3LP32-0N modules. The
wiring diagram is shown below.
Using a pair of twisted cable wires, connect all send/receive terminals A and B in
parallel.
For the other pair of twisted cable wires, connect both wires together at the SG
terminal of each module.
Connect the shield of the cable at the SHIELD terminal.
The lower end terminal of the module is not used. Do not connect any cable to this
terminal.
A
B
SG
SHIELD
T
erm
inat
ing
res
is
tor
Maximum total cab le length: 1 km
T
erm
inat
ing
re
s
is
tor
FA Link H2 module
FA Link H2 module
FA Link H2 module
A
B
SG
SHIELD
A
B
SG
SHIELD
Figure 3.6.3 External Wiring