CAUTION
•
When a tank filling (
Xn
) does not reach 100% of the height of the tank, the transmitter will calculate the
remaining part. This calculating method is linear and will only be used for the remaining part up to 100%.
Linearized Filling
Linear calculation up to 100%
•
It is not advisable to manually adjust the SPAN in program point P102 after a linearization has been
configured. If the SPAN is adjusted after a linearization configuration, a warning will appear on the screen
when entering P102.
•
When the a free linearization is used for measuring weight (Kg and Tons), a reliable accuracy cannot be
guaranteed due to external influences such as heat and tank wall expansion.
The change of Specific
Gravity due to different temperatures cannot be compensated by the pressure transmitter.
n
Simulation
After linearization is entered and saved, it is possible to perform a simulation. (Based on the saved linearization)
The transmitter will convert the entered mWc to hectoliters.
6.12 Burst Mode
The transmitter can be configured for Burst mode.
This
will enable continuously broadcasting standard
HART reply messages.
1.
Navigate to program point
P115 – Burst Mode
and push the navigation button to enter the
menu.
2.
A message appear on the screen, push to
enter this menu.
3.
Three choices appear on the screen:
“
0
”, “
1
” and “
2
”
4.
With these choices, three distinct types of
burst messages can be configured. Make a
choice, and push the button to confirm.
5.
Four choices appear on the screen:
Mode
Cntrl
,
Cmd number
,
Period
and
Trigger
With
these choices the chosen burst message (0,1
and 2) can be configured. Select
Mode Cntrl
,
and push to confirm.
6.
Two choices appear on the screen:
“
On
” and “
Off
”
•
Choose
On
to turn on burst mode.
•
Choose
Off
to turn off burst mode.
7.
Select Cmd number, and push to confirm.
Five choices appear on the screen:
•
Cmd 01:
Primary Variable
Burst mode
P112
•
Cmd 02:
Current and Percent of Range
•
Cmd 03:
Dynamic Variables and Current
•
Cmd 09:
Device Variables with Status
•
Cmd 48:
Additional Transmitter Status
Choose the preferable burst mode, and push
to confirm.
8.
Select
Period
, and push to confirm.
Two choices appear on the screen:
“
Max Time
” and “
Min Time
”
•
Select
Max Time
to set the maximum
amount of time when the message will
be send. This value can be set from 0.5
to 3600 seconds.
•
Select
Min Time
to set the minimum
amount of time when the message will
be send. This value can be set from 0.5
to 3600 seconds.
Enter the preferred value, and push to confirm.
9.
Select
Trigger
, and push to confirm.
Five choices appear on the screen:
•
Continuous:
The Burst message is
send continuously.
•
Windowed:
The Burst message is
triggered when the measured value
deviates more than the specified trigger
value.