6.11.2 Linearization Horizontal Tank (with Flat End)
1.
Navigate to
Hor. Tank.
with the navigation button, and push to confirm.
2.
Two choices appear on the screen:
Input
and
Simulate
3.
Select
Input
, and push to confirm.
4.
Six choices appear on the screen:
DISPLAY
DRAWING
EXPLANATION
Length
L
The length of the tank
Height 1
H1
The height of the tank
Height 2
H2
The diameter of the tank (with a cylindrical tank, this is equal to the height of the tank)
Height 3
H3
The height till the topside of the diaphragm (or weld-on nipple)
Height 4
H4
Value must be 0
Fill Height
FH
The maximum percentage of filling of the tank
5.
Fill in each value except Height 4, and confirm each selection with the control button.
The values must be
entered in meters.
6.
Select
SAVE
SAVE
to save the setting.
7.
The transmitter will return to the main menu.
n
Simulation
After linearization is entered and stored, it is possible to perform a simulation based on the entered values.
Based on the value entered in mWc, the transmitter will display the number of hectoliters (on the basis of the
specified linearization values).
1.
Navigate to program point
P111 – TANK LIN
, and push the navigation button to enter the menu.
2.
Navigate to
Hor. Tank.
with the navigation button, and push to confirm.
3.
Two choices appear on the screen:
Input
and
Simulate
4.
Select
Simulate
, and push to confirm.
5.
Fill in the desired value based on mWc, the number of hectoliters change directly with a change in the
value mWc.
L
H2
FH
H1
H3