<6. Explanation Programming Points>
Four choices appear on the screen for the
secondary readout on the main screen:
Current
,
Unit
,
Rate
and
Temperature
.
Sec. Time:
(Only available when using HART 7 Protocol)
An input screen to enter the date and time will
appear.
HART version:
Choice between:
HART 5.0
and
HART 7.0
.
6.9 Readout
In this menu, the readout on the display is
determined. This is the type of measurement that
appears on the home screen.
Factory Setting = Unit
1.
Navigate to program point P109 – READOUT,
and push the navigation button to enter the
menu.
2.
Nine choices appear on the screen:
Current:
Present current value (4-20mA)
Unit:
Pressure unit as chosen in P104
Percentage:
0-100%
Temperature:
Actual sensor temperature (°C
or F)*
*(Indication of process temperature, accuracy
depending on sensor position)
Hectoliter:
Number of hectoliters (only
possible in combination with linearization
P111)
Cubic meter:
Number of cubic meters (only
possible in combination with linearization
P111)
Liter:
Number of liters (only possible in
combination with linearization P111)
Kilogram:
Number of kilograms (only possible
in combination with linearization P111) After
selecting this readout the Specific Gravity of
the medium (SG = g/cm
3
) must be entered
with a value between 0.2 and 4.0 g/cm
3
.
The specific gravity will appear on the home
screen (g/cm
3
) under the primary chosen
readout. This readout will be indicated as a
linear measurement, and displayed by the
symbol on the home screen.
Readout
P1O9
Tons:
Number of tons (only possible in
combination with linearization P111)
After selecting this readout the Specific Gravity
of the medium (SG = g/cm
3
) must be
entered with a value between 0.2 and
4.0 g/cm
3
. This readout will be indicated as
a linear measurement, and displayed by the
symbol
on the home screen. The specific
gravity will appear on the home screen (g/cm
3
)
under the primary chosen readout.
3.
Navigate to the desired choice, confirm the
selection by pushing the navigation button.
The Save
icon will be displayed to indicate
that the setting is saved.
4.
The transmitter will return to the main menu.
CAUTION
•
For measuring weight (Kg and Tons), a
reliable accuracy cannot be guaranteed, the
transmitter cannot compensate for Specific
Gravity changes or any thermal increase or
decrease.
6.10 Current
Simulation
(4-20 mA)
The transmitter can simulate an output between
4-20 mA.
Using five predefined steps or a free selectable
value between 3
.
90 mA to 20
.
8 mA
1.
Navigate to program point
P110 – CURR
SIMU
, and push the navigation button to enter
the menu.
2.
Two choices appear on the screen: “
Set
” and
“
Free
”
3.
Choosing
Set
allows a value to be set in five
steps: 4, 8, 12, 16, 20 mA
•
By default the current simulation is
Not
active
, as shown in the display
•
Choose one of the five steps, and push
to confirm
•
The status on the display will change
to
Active
and the current simulation is
started for the selected step.
•
Push the navigation button to de-
activate the current simulation.
•
Move the navigation button to the left to
Curr sim.
P11O
Sec. Value: