IM 01C25C01-01E
7-1
7. OPERATION
7.
OPERATION
7.1 Preparation for Starting
Operation
The EJX210A flange mounted differential pressure
transmitter measures the levels or densities of liquids.
This section describes the operation procedure for the
EJX210A as shown in Figure 7.1 when measuring a
liquid level in an open tank.
(a) Confirm that there is no leak in the connecting part
of the transmitter mounting flange.
Remove the plastic dust cap placed in the process
connector (low pressure side).
(b) Turn ON power and connect the communicator.
Open the terminal box cover and connect the
communicator to the and – terminals.
(c) Using the communicator, confirm that the transmit-
ter is operating properly. Check parameter values or
change the setpoints as necessary.
See IM 01C25T03-01E (BRAIN communication) or
IM 01C25T01-01E (HART communication) for
communicator operation. If the transmitter is
equipped with an integral indicator, its indication
can be used to confirm that the transmitter is
operating properly.
F0701.EPS
Open Tank
Figure 7.1 Liquid Level Measurement
Confirming that Transmitter is Operating
Properly
Using the BT200
• If the wiring system is faulty, ‘communication error’
appears on the display.
• If the transmitter is faulty, ‘SELF CHECK ERROR’
appears on the display.
communication error
PARAM
C60:SELF CHECK
ERROR
Communication error
(Faulty wiring)
Self-diagnostic error
(Faulty transmitter)
DATA
DIAG
PRNT
ESC
F0702.EPS
Using the integral indicator
• If the wiring system is faulty, the display stays blank.
• If the transmitter is faulty, an error code is displayed.
Self-diagnostic error on
the integral indicator
(Faulty transmitter)
F0703.EPS
NOTE
If any of the above errors are indicated on the
display of the integral indicator or the communi-
cator, refer to subsection 8.5.3 for corrective
action.