IM 01C25B01-01E
9-19
9. GENERAL SPECIFICATIONS
SUPPLY
CHECK
or
ALARM
+
–
+
–
●
Terminal Configuration
Power supply and output terminal
External indicator (ammeter) terminal
*1*2
or
Status contact output terminal
*2
(when /AL is specified)
Ground terminal
Communication
terminals (BT200 etc.)
connection hook
●
Terminal Wiring
*1: When using an external indicator or check meter, the internal
resistance must be 10
or less. A check meter or indicator
cannot be connected when /AL option is specified.
*2: Not available for fieldbus communication type.
Check meter
connection hook
*1*2
SUPPLY –
CHECK – or ALARM –
CHECK + or
ALARM +
+
–
F0911.EPS
< Factory Setting >
Tag Number
Output Mode
Amplifier
Damping
*2
As specified in order
‘Linear’ unless otherwise specified in order
‘2 sec.’ or as specified in order
Display Setting
As specified in order
'0 to 25 MPa' for M and H capsule of
EJX110A, '0 to 16 MPa' for L capsule,
and '0 to 32 MPa' for EJX130A.
Display unit is selectable from the units
listed in above 'Calibration Range Units'.
Calibration Range
Units
Designated differential pressure value
specified in order. (%, Engineering unit or
user scaled value.) Display mode 'Linear'
or 'Square root' is also as specified in
order.
As specified in order
Selected from the followings. Only one
unit can be specified.
[Differential/gauge pressure transmitter]
mmH
2
O, mmH
2
O(68˚F),mmAq, mmWG,
mmHg, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm
2
, kgf/cm
2
, inH
2
O,
inH
2
O(68˚F),inHg, ftH
2
O, ftH
2
O(68˚F) or
psi.
[Absolute pressure transmitter]
torr, Pa abs, hPa abs, kPa abs, MPa abs,
mbar abs, bar abs, mmH
2
O abs,
mmH
2
O(68˚F) abs, mmHg abs,
gf/cm
2
abs, kgf/cm
2
abs, inH
2
O abs,
inH
2
O abs(68˚F), inHg abs, ftH
2
O abs,
ftH
2
O abs(68˚F) , atm, or psia.
Calibration Range
Upper Range Value
Calibration Range
Lower Range Value
T0915.EPS
Static Pressure
Display Range
*1
*1: For differential pressure transmitters only.
*2: To specify these items at factory, /CA or /CB option is
required.