IM 01C25B01-01E
9-11
9. GENERAL SPECIFICATIONS
Item
Description
Code
Painting
Color change
Coating change
Lightning protector
Calibration units
*2
Long vent
*3
Output limits
and failure operation
*4
P
X2
A
K1
D1
D3
D4
U1
C1
(See Table for Span and
Range Limits.)
Terminal cover only
Anti-corrosion coating
Degrease cleansing treatment
P calibration (psi unit)
bar calibration (bar unit)
M calibration (kgf/cm
2
unit)
Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code
K1, K2, K5, and K6: 130 mm. Material: 316SST.
Failure alarm down-scale : Output status at CPU failure and hardware error is –5%,
3.2mA DC or less.
K2
Degrease cleansing treatment and with fluorinated oilfilled capsule.
Operating temperature
20 to 80
C( –4 to 176
F)
Oil-prohibited use
*1
European Pressure Directive
*7
PED 97/23/EC
Category: III, Module: H, Type of Equipment; Pressure Accessory-Vessel, Type of Fluid;
Liquid and gas, Group of Fluid: 1 and 2
PE3
K5
Degrease cleansing treatment and dehydrating treatment
K6
Degrease cleansing treatment and dehydrating treatment with fluorinated oilfilled capsule.
Operating temperature
20 to 80
C( –4 to 176
F)
Oil-prohibited use
with dehydrating treatment
*1
N1
Without drain and vent plugs
Body option
*5
Data configuration at factory
*6
N2
N1 and Process connection, based on IEC61518 with female thread on both sides of
cover flange, with blind kidney flanges on back.
N3
N2 and Material certificate for cover flange, diaphragm, capsule body, and blind kidney
flange
Stainless steel tag plate
N4
304SST tag plate wired onto transmitter
T09913.EPS
Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically
safe type.)
Allowable current: Max. 6000 A ( 1
40
s ), Repeating 1000 A ( 1
40
s ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Both sides of amplifier covers, Munsell 7.5 R4/14
PR
NAMUR NE43 Compliant
Output signal limits : 3.8 mA to
20.5 mA
Failure alarm down-scale : Output status at CPU
failure and hardware error is –5%, 3.2 mA DC or less.
Failure alarm up-scale : Output status at CPU
failure and hardware error is –110%, 21.6 mA or more.
C2
C3
Capsule fill fluid
K3
Fluorinated oil filled in capsule
Data configuration for HART communication type
Data configuration for BRAIN communication type
CA
CB
Software damping, Descriptor, Message
Software damping
Transistor output (sink type)
Contact rating :10.5 to 30 VDC, 120 mA DC(max) Low level : 0 to 2 VDC
AL
Status output
*8
*1: Applicable for Wetted parts material code S.
*2: The unit of MWP (Max. working pressure) on the name plate of the housing is the same unit as specified by Option code D1, D3, and D4.
*3: Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S.
*4: Applicable for output signal code D and E. The hardware error indicates faulty amplifier or capsule.
*5: Applicable for Wetted parts material code S; Process connection code 3, 4, and 5; Installation code 9; and Mounting bracket code N.
Process connection faces on the other side of zero adjustment screw.
*6: Also see ‘Ordering Instructions’.
*7: Applicable for M and H capsule of EJX110A, and all the range of EJX130A and EJX440A.
*8: Not applicable for output signal code F.