<5. Wiring>
46
IM 01C25A01-01E
Procedure
(1) Disassemble the cable gland: loosen the running
coupler to separate the backnut from the entry.
(2) Remove the protection cap over the transmitter
electrical connection and install the entry on the
electrical connection. Note that a non-hardening
sealant should be applied to the threads for a 1/2 NPT
connection and a gasket should be used for an M20
connection.
F0517.ai
(3) Pass the RTD cable through the running coupler and
backnut assembly.
F0518.ai
(4) Insert the RTD cable and firmly plug its connector into
the connecting port in the transmitter's terminal box.
F0519.ai
(5) Align the running coupler on the entry.
F0520.ai
(6) Turn the running coupler until the seal in the entry
comes into contact with the RTD cable.
F0521.ai
(7) Rotate the running coupler another half turn to
securely tighten the seal on the RTD cable.
(8) Use a protection conduit, if necessary.
In this case, insert the cable through the conduit and
attach it to the Backnut.
CAUTION
After the cable is secured as explained above, do not
tighten the running coupler any further; to do so could
damage the RTD connection.
Do not pull the cable or subject it to excessive
mechanical shock.
5.4.2 Connecting Shielded Cable for Con-
duit Use (External temperature input
code: -B, -C, and -D)
• RTD connection components: EJX multivariable
transmitter and RTD cable
F0522.ai
Procedure
(1) Remove the protection cap protecting the RTD
electrical connection and insert the RTD cable.
F0523.ai
(2) Remove the cap protecting the connecting port. Then
insert the RTD cable and firmly plug the connector
into the connecting port in the transmitter's terminal
box.
(3) Insert the cable through the conduit and attach it to
the RTD electrical connection.
CAUTION
Do not pull the cable or subject it to excessive
mechanical shock.