<2. Handling Cautions>
10
IM 01C25A01-01E
c. FM Intrinsically Safe/Nonincendive for
Fieldbus Type for EJX9
0A
EJX multivariable transmitter with optional code
/FS15 are applicable for use in hazardous locations.
Note 1.
• Applicable Standard:
Class 3600:2011, Class 3610:2010,
Class 3611:2004, Class 3810:2005
ANSI/ISA-60079-0:2009, ANSI/ISA-60079-11:2009,
ANSI/ISA-60079-27:2006
NEMA 250:1991
• Rating
Intrinsically Safe with Entity/FISCO for Class I, II, III
Division 1 Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive field wiring/FNICO for Class I, II
Division 2 Groups A, B, C, D, F, G T4
Class III Division 1 T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –40 to 60°C
• Enclosure: Type 4X
• Electrical Connection: 1/2 NPT female, M20
female
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM026-A12.