<2. Handling Cautions>
2-4
IM 01C27C01-01EN
2.8 Installation of an Explosion-
Protected Instrument
If a customer makes a repair or modification to an
intrinsically safe instrument and the instrument is
not restored to its original condition, its intrinsically
safe construction may be compromised and the
instrument may be hazardous to operate. Please
contact Yokogawa before making any repair or
modification to an instrument.
CAUTION
This instrument has been tested and certified
as being intrinsically safe. Please note that
severe restrictions apply to this instrument’s
construction, installation, external wiring,
maintenance and repair. A failure to abide by
these restrictions could make the instrument a
hazard to operate.
WARNING
The battery pack may be replaced in a
hazardous area. The battery pack has
surface resistivity greater than 1G ohm and
must be properly installed in the enclosure
of the transmitter. Care must be taken during
transportation to and from the point of installation
to prevent electrostatic charge build-up.
2.8.1 FM Approval
Caution for FM intrinsically safe type. (Following
contents refer “DOC. No. IFM037-A20”)
Note 1. Model EJX Series Differential, gauge
and absolute pressure transmitters with
optional code /FS17 are applicable for use
in hazardous locations.
• Applicable Standard: Class 3600, Class
3610, Class 3611, Class 3810, NEMA 250,
ANSI/ISA-60079-0, ANSI/ISA-60079-11
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1,
Class I, Zone 0, in Hazardous Locations, AEx
ia IIC
• Nonincendive for Class I, Division 2, Groups
A, B, C & D, Class II, Division 2, Groups F &
G and Class III, Division 1, Class I, Zone 2,
Groups IIC, in Hazardous Locations.
• Enclosure: NEMA 4X (Indoors and outdoors).
• Temperature Class: T4
• Ambient temperature: -50 to 70°C
Note 2. Installation
• Installation should be in accordance with
ANSI/ISA-RP12.06.01 and the National
Electric Code (NFPA 70).
• Dust-tight conduit seal must be used when
installed in a Class II, III, Group E, F and G
environments.
• Note a warning label worded
“SUBSTITUTION OF COMPONENTS MAY
IMPAIR INTRINSIC SAFETY,” and “INSTALL
IN ACCORDANCE WITH DOC. NO.
IFM037-A20”.
[Installation Diagram]
F0204.ai
Transmitter
[Intrinsically Safe]
Class I, II, III, Division 1,
Groups A,B,C,D,E,F,G
Class I, Zone 0
in Hazardous (Classified)
Locations
AEx ia IIC
[Nonincendive]
Class I, II, Division 2,
Groups A,B,C,D,F,G
Class III, Division 1.
Class I, Zone 2, Group IIC,
in Hazardous (Classified)
Locations
Antenna
(*1)
Arrester
(*1, *2)
*1: These apparatus are simple apparatus.
*2: Arrester may not be connected.
Antenna Connector
Battery Pack
Hazardous Location
Note 3. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void FM
Approvals approval.
Note 4. Battery Pack
USE ONLY BATTERY PACK YOKOGAWA
F9915MA OR F9915NS.
Note 5. Special Conditions for safe use
POTENTIAL ELECTROSTATIC CHARGING
HAZARD-SECURE DISTANCE OF 100MM
FROM ANTENNA.
DO NOT OPEN WHEN CL II, III, DIV 1,2
ATMOSPHERE IS PRESENT.