INDOOR UNIT INSTALLATION
Tightening torque table:
Pipe size
Φ
6.25 (1/4")
Φ
9.52 (3/8")
Tightening torque (N
·
m)
15~20
30~40
Power supply and wiring requirement
AC 208/230V. If voltage is over, may cause the parts of electric equipment to become damaged. If the voltage
is too low, this may cause the compressor to shake thus causing damage to the cooling system.
2) User power supply should be provided a reliable grounding connect. (see earth requirement)
1) Power frequency of air conditioner should be 60 Hz, voltage:
1) Should have a reliable earth connection (see earth connection requirement)
2) Screw of wire should be tight, damaged screw should be changed. ( Self tapping screws cannot be used on
an electrical connection.)
3) The provided wire should be used. Please do not change the wire, length and end of it. If you need to adjust,
please contact the local service center.
4) Please do not connect the plug with the non-plug wire by yourself.
5) Indoor and outdoor electrical connecting wire should not be pulled too tightly or twisted.
Electrical connection requirement
ELECTRICAL WIRING
Φ
12.7 (1/2")
Φ
15.9 (5/8")
50~55
60~65
Pipe size
Tightening torque (N
·
m)
INDOOR UNIT CONTROL BOX & WIRING TERMINALS
Remove the control box cover and install the connection cord to the wiring terminals. Must match terminal
number for each wire at both indoor unit and outdoor unit wiring terminal.
Note:
* The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper
tube.
* An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current
device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
CONNECTION OF REFRIGERANT PIPE
* Besure to use both a spanner and torque wrench together as shown in the drawing, connecting or
disconnecting pipes to/from the unit.
* Refer to table 1 to determine the proper tightening torque (over tightening may damage the flare and cause
leaks.)
* When connecting the flare nut, coat the flare both inside and outside with refrigerating machine oil and initially
tighten by hand 3 or 4 turns.
* Check the pipe connector for gas leaks, then insulate it as shown in the drawing below.
* Use sealing pad (11) to wrap joint between gas pipe and the insulation(8).
* The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
INDOOR UNIT INSTALLATION
Caution:
(1)
is not on. If moved by hand, it may be damaged.
(2) The grille assembly is directional relative to the
air conditioner body.
(3) Install so that there is no gap between the grille
assembly and the air conditioner body.
The louver angle cannot be changed if the power
(3) Open the intake grille so that it is at an angle of
o
o
20 to 40 ,and then remove the grille.
(2) Remove the grille hook screws, and then open
the intake grille.
2.Removing the intake grille
(1) Slide the two grille stoppers inward, and then
open the intake grill.
FINISHED INSTALLATION ABOVE CEILING
Mounting-Threaded Rod Hung on Rafters
Mounting-Threaded Rod Hung on Truss
Control box cover