PIPING GUIDE
Set the packed pipes in a
vertical position and then
unwind them slowly.
Do not unwind only one end of
the coiled pipes.
Use pulley or a bending tool
to ensure a safe bending
radius.
Do not make any sharp or small
radius bends.
May also use rolling wheel to
reduce internal pipe tension
and avoid possible
deformation.
Do not bend long sections of
pipe without using bending
tools.
Use an elbow tool for
consistent bending radius.
Do not make bends that are
less than 90 degrees.
Maintain the minimum
bending radius.
Do not bend shot pipes.
PIPING AND WIRING SIZES-UNITS
Model
Liquid /
Gas Line
Min - Max
Length/
+/-Elevation
Power Wire Min.
Disconnect Switch Box to
Outdoor Unit
Power/ Control Wire Min.
Outdoor Unit to Indoor Unit
Recommended HVAC
Circuit Breaker/Fuse
AMP
(to Outdoor Unit)
09K
1/4" & 3/8"
15 - 49.2 / 16.4
+/- 24V 12AWG
(N)/2/3/G/F/V, 24V, 7×AWG16
20
12K
1/4" & 3/8"
15 - 49.2 / 16.4
+/- 48V 10AWG
(N)/2/3/G/F/V, 48V, 7×AWG16
30
18K
1/4" & 1/2"
15 - 49.2 / 16.4
+/- 48V 10AWG
(N)/2/3/G/F/V, 48V, 7×AWG16
40
24K
1/4" & 5/8"
15 - 49.2 / 16.4
+/- 48V 8AWG
(N)/2/3/G/F/V, 48V, 7×AWG16
50
The indoor unit and the outdoor unit can be at different heights either above or below each other. The height for the
difference must follow the stated requirements shown in the table below.
Keep bending of the piping line to a minimum to avoid any possible negative impacts on the performance of the units.
Make a P-trap if the elevation drop difference is more than 24 inches, as illustrated below.